Agentic Lightweight Consensus for Resilient Monitoring and Control of Modern Data Centers in Smart Cities

Smart Cities / MDPI · Domenico Furno, Vincenzo Loia

A 2026 Smart Cities (MDPI) paper presents a two-path data centre control architecture that fuses sensor data with a reliability-based fuzzy-preference OWA operator and lets an LLM supervisor only propose actions a verifier admits; 1890 simulation scenarios.

On this page

Overview

The paper proposes a two-path agentic architecture for data centre control loops that must reconcile noisy, missing or deliberately deceptive telemetry before acting autonomously. A deterministic fast path fuses sensor reports with a reliability-based fuzzy-preference OWA operator (FPR-OWA) and a persistent consensus-reaching process (CRP), while an optional reactive or LLM supervisor can only propose typed actions that a deterministic verifier must admit.

Evaluation covers 1890 indexed simulation scenarios and seven attack families. No estimator dominates: averaging gives the lowest global error and sensor redundancy explains most accuracy variation, while FPR-OWA with CRP gives the strongest anomaly-diagnostic signal. No unsafe execution was observed in verifier-gated episodes and all 24 deterministic fault-injection cases passed; the authors state these are empirical, not formal, guarantees. Persistent CRP median latency is below 0.30 ms at 100 sensors. Hardware validation, production authentication and energy measurement remain future work.

Key points

  1. The architecture has two paths: a deterministic fast path (FPR-OWA and persistent CRP) and an optional LLM or reactive supervisor that can only propose.
  2. Supervisor proposals must pass a deterministic verifier before the modelled actuation step.
  3. Across 1890 indexed simulation scenarios and seven attack families, no estimator dominates; averaging gives the lowest global error.
  4. Sensor redundancy explains most of the accuracy variation; FPR-OWA with CRP gives the strongest anomaly-diagnostic signal.
  5. No unsafe execution was observed in verifier-gated episodes and 24 deterministic fault-injection cases passed; these are empirical, not formal, guarantees.
  6. Recovery is delayed under common-mode sensor bias; persistent CRP median latency is below 0.30 ms at 100 sensors.
  7. Hardware validation, production authentication and energy measurement remain future work.

Using it in design

  • In autonomous cooling control, pass AI proposals through a deterministic safety verifier before commands are applied.
  • Plan sensor redundancy as the main design lever for temperature and flow measurement accuracy.
  • Add independent measurement and cross-checking for common-mode sensor bias.
  • Results are simulation-based; plan hardware validation and authentication before field use.

Who should read it

Engineers and researchers designing data centre control systems and AI-assisted cooling automation.

Publication details

Authors
Domenico Furno; Vincenzo Loia
Publisher
Smart Cities / MDPI
Year
2026
Document number
9(9), 157
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Article-specific copyright footer links CC BY 4.0. Generic dc.rights metadata says BY 3.0; the explicit article footer is retained as the licensing evidence. Attribution and third-party credit conditions apply.

Citation

Domenico Furno; Vincenzo Loia (2026). Agentic Lightweight Consensus for Resilient Monitoring and Control of Modern Data Centers in Smart Cities. Smart Cities / MDPI. 9(9), 157. https://doi.org/10.3390/smartcities9090157

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.