Medium voltage increases savings to power multistory data centers

Consulting-Specifying Engineer · Bruce Young

Bruce Young's article makes the case for 13.2 kV distribution in multistory data centres instead of long 480 V runs, using a case study, and lists the control and protection features needed for reliable MV operation.

On this page

Overview

This 2023 article by Bruce Young was published in Consulting-Specifying Engineer. It argues that 13.2 kV distribution should be used inside multistory data centres instead of long 480 V runs. The argument rests on a case study with a centralized system and dual-ended main-tie-tie-main substations in physically separated rooms.

The author quantifies the savings through conduit and copper: at 13,200 V one 4 in. conduit can carry up to about 4,000 kW, while the same load at 480 V can need up to twelve 4 in. conduits or busway. In multistory buildings such runs along the floors raise conduit and copper cost markedly, so medium-voltage distribution becomes more economical over long distances.

The article lists the control and protection features needed for reliable MV operation. Parallel redundant PLCs in separate enclosures and redundant I/O remove control single points of failure. Multiple control-power sources are provided, switched by an 83 relay, with one fed directly from the on-site generator, and a black-start relay is included. Neutral grounding resistors and snubbers also appear in the list.

Safety practices centre on de-energizable paths and remote operation outside the arc-flash zone. Close-coupled transformers are protected by snubbers against switching transients produced by vacuum breakers with VPI transformers. The article is an expert opinion piece based on a single case scenario; its conclusions cannot be applied directly to every facility, but it gives a concrete checklist for evaluating MV distribution.

Key points

  1. At 13,200 V one 4 in. conduit can carry up to about 4,000 kW; the same load at 480 V can need up to twelve 4 in. conduits or busway.
  2. Substations use dual-ended main-tie-tie-main arrangements with each side in a physically separated room.
  3. Parallel redundant PLCs in separate enclosures and redundant I/O remove control single points of failure.
  4. Multiple control-power sources are switched by an 83 relay, one fed directly from the on-site generator, plus a black-start relay.
  5. Snubbers protect close-coupled transformers from switching transients produced by vacuum breakers with VPI transformers.
  6. Safety practices rely on de-energizable paths and remote operation outside the arc-flash zone.
  7. Neutral grounding resistors are also named among MV control and protection features.
  8. The article is an expert opinion based on a single case scenario.

Using it in design

  • Assess an MV distribution template (13.2 kV, main-tie-tie-main, separated rooms) for multistory halls and compute conduit and cable quantities against 480 V.
  • Suggest snubbers when vacuum breakers feed close-coupled dry-type transformers.
  • Require redundant control power and black-start provisions for MV gear in concurrently maintainable designs.
  • Add remote operation and de-energizable paths to the design checklist.

Who should read it

Electrical design engineers and consultants planning power distribution for multistory data centres.

Publication details

Authors
Bruce Young
Publisher
Consulting-Specifying Engineer
Year
2023
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Bruce Young (2023). Medium voltage increases savings to power multistory data centers. Consulting-Specifying Engineer. https://www.csemag.com/medium-voltage-increases-savings-to-power-multistory-data-centers/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.