Data Center Continuous (DCC) Ratings: A comparison of DCC ratings, ISO definitions and Uptime requirements

Cummins · David Matuseski

Cummins white paper arguing that a manufacturer-defined unlimited-hours rating (Cummins DCC) fits Uptime Tier III/IV data centres better than the ISO 8528-1 continuous, prime or standby ratings.

On this page

Overview

Under Uptime Tier III/IV the generators are the primary source: they must carry the entire data-centre load and have no limit on run hours. The ISO 8528-1 run-time limits are: COP unlimited at 100 % for a constant load, PRP unlimited only at 70 % average or less, and ESP limited to 200 h/year with 70 % average or less over 24 h. Uptime accepts a manufacturer's certified unlimited-duration capacity, including site-specific ratings via a manufacturer letter (Tier Standard: Topology sec. 3.3).

The ISO Data Centre Power (DCP) rating added in 2018 is stated as not appropriate for Tier III/IV because it references utility availability and prohibits prolonged utility-parallel operation. In the example, four 2,500 kW DCC-rated sets meet a demand that would need five 2,500 kW ISO Prime-rated sets with no run-time limit.

Low load is the second argument: diesel engines should run above 30 % of maximum horsepower to avoid wet-stacking, valve wear and turbo degradation. In an example of five 1.6 MW sets at 36-39 % system load, COP-rated sets run below 30 % of max hp while DCC-rated sets run above it. QSK95-based sets offer ratings up to 3.5 MW (ISO 8528-1). The paper is a manufacturer defending its own rating, so the comparisons rest on Cummins product classes.

Key points

  1. Under Uptime Tier III/IV generators are the primary source: they carry the whole load with no run-hour limit.
  2. ISO 8528-1: COP unlimited at 100 % constant load; PRP unlimited only at <= 70 % average; ESP 200 h/year with <= 70 % average over 24 h.
  3. The 2018 ISO DCP rating is not appropriate for Tier III/IV: it references utility availability and prohibits prolonged parallel operation.
  4. Uptime accepts a manufacturer-certified unlimited-duration capacity, including site-specific letters (Tier Standard: Topology sec. 3.3).
  5. Four 2,500 kW DCC sets meet demand that would need five 2,500 kW ISO Prime sets.
  6. Run above 30 % of maximum hp to avoid wet-stacking, valve wear and turbo degradation.
  7. At 36-39 % system load with five 1.6 MW sets, COP-rated sets fall below 30 % while DCC-rated sets stay above.
  8. QSK95-based sets offer ratings up to 3.5 MW (ISO 8528-1).

Using it in design

  • For generator selection, record rating table keyed by class {ESP, PRP, COP, DCP, DCC/manufacturer-unlimited} rather than a single kW value.
  • For Tier III/IV targets, size N on a rating with unlimited run hours at design load (COP, DCC or a site-specific letter), reject ESP and DCP, and allow PRP only at 70 % average or less.
  • Warn when the expected normal load per set is below 30 % of the selected rating, and suggest load-bank provisions or fewer, larger sets.

Who should read it

Electrical engineers selecting the generator rating class and set count for Tier III/IV targeted data centres.

Related standards

  • ISO 8528-1
  • Uptime Institute Tier Standard: Topology

Publication details

Authors
David Matuseski
Publisher
Cummins
Year
2025
Document number
Bulletin 5600406
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

David Matuseski (2025). Data Center Continuous (DCC) Ratings: A comparison of DCC ratings, ISO definitions and Uptime requirements. Cummins. Bulletin 5600406. https://mart.cummins.com/imagelibrary/data/assetfiles/0059642.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.