Energy Performance Study of a Data Center Combined Cooling System Integrated with Heat Storage and Waste Heat Recovery System
Buildings (MDPI AG) · Chaohui Zhou, Yue Hu et al.
A TRNSYS model of a chilled-water-cooled data centre in Guangzhou, China, combining natural-source free cooling, chillers with cooling towers, a water-source heat pump that recovers heat from the return chilled water into hot-water storage tanks, and rooftop PV.
CC BY 4.0: share with attribution
On this page
Overview
The study proposes an integrated energy system for a data centre with different renewable energy sources and waste heat recovery, able to consider partial and unsteady IT load. The modelled data centre has 4 computer rooms and 2 equipment rooms, a computer-room area of 1867.4 m² and 740 racks, each 0.6 × 1.2 × 2.2 m with a maximum power of 4 kW. A full year was simulated and the integrated system compared with a conventional reference plant.
Free natural-resource cooling covers about 28% of the cooling demand. Against the reference case the integrated system saves 16.4% of energy, raises system COP from 3.88 to 4.64, lowers PUE from 1.36 to 1.30 and cuts electricity expenses by 23.45%. The water-source heat pump absorbs 3,575,709.597 kWh of heat from the data centre per year and provides 4,587,711.45 kWh of heating energy. Two 500 m³ hot-water tanks store recovered heat; in winter they consistently supply hot water at 45 °C, and in summer, with the heat pump off, outlet water stays at around 30 °C.
Rooftop PV generates about 370,000 kWh per year, about 8% of the data centre's total electricity use. The study is a useful template for annual-hour simulation of heat recovery from chilled-water return streams.
Limits: the site is a low-density air-cooled hall (at most 4 kW per rack), so results do not transfer directly to high-density AI racks. More heat can be recovered as heating demand increases; heat recovery and PV share were simulated for a single facility and climate.
Key points
- The modelled Guangzhou data centre has 4 computer rooms and 2 equipment rooms, a computer-room area of 1867.4 m² and 740 racks, each 0.6 × 1.2 × 2.2 m with a maximum power of 4 kW.
- Free natural-resource cooling covers about 28% of the cooling demand.
- Against the reference case the integrated system saves 16.4% of energy, raises system COP from 3.88 to 4.64, lowers PUE from 1.36 to 1.30 and cuts electricity expenses by 23.45%.
- The water-source heat pump absorbs 3,575,709.597 kWh of heat from the data centre per year and provides 4,587,711.45 kWh of heating energy.
- Two 500 m³ hot-water tanks store recovered heat; in winter they supply hot water at 45 °C, and in summer with the heat pump off outlet water stays at around 30 °C.
- Rooftop PV generates about 370,000 kWh per year, about 8% of the data centre's total electricity use.
Using it in design
- Assess heat recovery from chilled-water return with a water-source heat pump and hot-water storage in annual-hour simulation; match the winter and summer outlet temperature difference (45 and 30 °C) to the user's need.
- Verify the free natural-resource cooling share (here 28%) with climate data and report the PUE gain (1.36 to 1.30) separately from the heat recovery and PV contribution.
- Label results as low-density (at most 4 kW per rack) air-cooled hall results; do not transfer them directly to high-density racks.
Who should read it
Engineers designing waste-heat recovery from chilled-water return and integrated energy systems.
Document contents
- 1. Introduction (1.1 Literature Reviews, 1.2 Research Gaps and New Contribution of This Study)
- 2. Methodology (2.1 Model of Data Center, 2.4 Simulation Model, 2.5 Model Validation)
- 3. Results and Discussion (3.1 System Energy Consumption, 3.2 System Cooling Capacity, 3.3 Waste Heat, 3.4 System Electricity Balance, 3.5 System Energy Efficiency)
- 4. Conclusions
Read the document
dc-cooling-heat-storage-waste-heat-2025.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Chaohui Zhou; Yue Hu; Rujie Liu; Yuce Liu; Meng Wang; Huiheng Luo; Zhiyong Tian
- Publisher
- Buildings (MDPI AG)
- Year
- 2025
- Volume
- 15
- Issue
- 3
- Pages
- 326
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1 states the article is open access under the Creative Commons Attribution (CC BY 4.0) licence; MDPI publishes all articles under CC BY 4.0.
Citation
Chaohui Zhou; Yue Hu; Rujie Liu; Yuce Liu; Meng Wang; Huiheng Luo; Zhiyong Tian (2025). Energy Performance Study of a Data Center Combined Cooling System Integrated with Heat Storage and Waste Heat Recovery System. Buildings (MDPI AG). 15(3), 326. https://doi.org/10.3390/buildings15030326
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.