White paperFree to read2014

Three-phase UPS Topology and Efficiency Enhancement

Delta Electronics, Inc. · Liao Jen-ch'uan (Delta Electronics), Kuo Ch'ao-lung (Delta Electronics)

A 2014 Delta Electronics white paper on raising three-phase double-conversion UPS efficiency through PFC and inverter topology, control, switch selection and ECO mode; a measured 200 kVA unit reaches 96.43% (double conversion) and 99.17% (ECO).

On this page

Overview

The paper opens with why efficiency matters, using a 200 kW example: raising efficiency from 92% to 96% saves about 80,000 kWh a year at full load, and the lower heat also cuts air-conditioning cost. It then introduces UPS types (offline, line-interactive, online) and the basic structure of a three-phase online UPS: bypass static switch, PFC, inverter, inverter static switch and charger.

The regulation section summarises China's CQC norms (April 2011), the European norms (March 2011) and the draft US Energy Star norms. CQC sets 92% normal efficiency for large online UPS above 100 kVA; in the European norms a 200 kVA UPS must reach 90% at 25% load, 92.5% at 50% load and 93.5% at 75% and 100% load; the Energy Star limit for a 200 kVA VFI unit is 92.58%.

The technical sections compare four PFC topologies (two-switch three-level, six-switch, three-level, and Delta's patented four-switch design) and three inverter topologies (isolated full-bridge, two-level, three-level). In the control section, third-harmonic injection raises DC bus utilisation from 0.866 to 1; on a 380 Vac system the needed bus voltage falls from 620 V to 540 V and switching loss for a 200 kW, 5 kHz inverter drops by 250 W.

This is a manufacturer paper and it highlights Delta's patented topologies, yet it shows with numerical examples how power semiconductor, switching frequency, bus voltage and magnetics choices affect efficiency. The conclusion reports a 200 kVA UPS measured by a certification institute at a peak of 96.43% in double conversion and 99.17% in ECO mode.

Key points

  1. Raising a 200 kW UPS from 92% to 96% efficiency saves about 80,000 kWh a year at full load.
  2. Efficiency ranks offline > line-interactive > online; power quality ranks the other way round.
  3. The European norms require 200 kVA units to reach 90% at 25% load, 92.5% at 50% load and 93.5% at 75% and 100% load.
  4. The Energy Star draft sets the limit for a 200 kVA VFI (online) UPS by the formula 0.0099 x ln(P) + 0.805, about 92.58%; CQC sets 92% above 100 kVA.
  5. Third-harmonic injection lowers the bus voltage requirement from 620 V to 540 V; for a 200 kW, 5 kHz inverter switching loss falls by 250 W.
  6. IGBT loss at 2 kHz is about one fifth of that at 20 kHz; losses between different vendors' IGBT modules can differ by up to 20%.
  7. Double-conversion efficiency is typically 92-94%; ECO mode raises it above 98% but carries a transfer risk at mains outage.
  8. A 200 kVA UPS measured at a certification institute reached a peak of 96.43% in double conversion and 99.17% in ECO mode.

Using it in design

  • Ask in the UPS specification for the efficiency curve at 25%, 50%, 75% and 100% load, not one peak figure; data-centre UPS units mostly run at partial load.
  • Put the efficiency difference into total cost of ownership, including cooling; a 4-point difference at 200 kW is about 80,000 kWh a year.
  • If ECO mode is to be used, assess transfer time and transfer-failure risk against the sensitivity of the load.
  • When comparing products, take PFC and inverter topology, switching frequency and bus voltage from the data sheet and judge them for input harmonic distortion and efficiency.
  • Settle at bid stage which norm (CQC, European, Energy Star) and which load points the efficiency figures refer to.

Who should read it

Electrical designers selecting UPS, engineers doing energy-efficiency and total-cost-of-ownership analysis, and UPS power-electronics developers.

Document contents

  1. Introduction
  2. Basic Topologies of UPS Systems
  3. International Regulations on UPS Efficiency
  4. Topology of PFC
  5. Topology of Inverters
  6. UPS Control Methods
  7. Selection of Power Switch and Magnetic Components
  8. High Efficiency ECO Mode Operation
  9. Conclusions

Related standards

  • IEC 62040-3
  • EU Code of Conduct on AC UPS Efficiency
  • ENERGY STAR UPS

Publication details

Authors
Liao Jen-ch'uan (Delta Electronics); Kuo Ch'ao-lung (Delta Electronics)
Publisher
Delta Electronics, Inc.
Year
2014
Document number
WP0001
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Delta Power Solutions white paper, free PDF; no open licence. Year from PDF metadata (Oct 2014).

Citation

Liao Jen-ch'uan (Delta Electronics); Kuo Ch'ao-lung (Delta Electronics) (2014). Three-phase UPS Topology and Efficiency Enhancement. Delta Electronics, Inc.. WP0001. https://www.deltapowersolutions.com/media/download/White-Paper_3-phase-UPS-topology-and-efficiency-enhancement_WP0001_en-us.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.