Overview of Green Energy Strategies and Techniques for Modern Data Centers
Delta Power Solutions
Delta Power Solutions' WP0014 technical article lists seven strategies to improve PUE; in a 200 kVA example a high-efficiency modular UPS saves about 5% electricity over a legacy UPS at light load.
On this page
Overview
This vendor technical article proposes assessing PUE as the first step in energy efficiency and presents PUE as a consistent and repeatable indicator. In the Uptime Institute's 2014 survey the industry average PUE is 1.7 (1.67 in 2013, 1.8 in 2012). The article notes that power cost ranks second only to personnel in data-centre total cost of ownership and that many centres still use no efficiency indicator; although PUE is debated, it remains the main measure of infrastructure efficiency.
Seven strategies are given: regular hardware audits, routine PUE measurement, hardware upgrades and server efficiency, improved cooling efficiency, raising data-centre temperature, DCIM and clean energy. In hardware audits, idle 'comatose' servers stand out: Barclays unplugged 9,124 unnecessary servers in 2013 and cut its power bill by $4.5 million. On UPS, transformerless modular UPS is stressed for scalability and light-load efficiency; N+X or 2N redundancy often leaves load at 30 to 40% or lower.
Cooling covers airflow management, higher ambient temperature and free cooling. An EPA study found effective hot and cold air containment reduced fan power by 25% and chiller power by 20%. ASHRAE's recommended range is 18 to 27 degrees C; an Intel study reports each 1 degree C increase in ambient temperature cuts cooling cost by about 4%. A high-temperature chilled water system raises supply water above the conventional 7 degrees C.
Google's 1.12 PUE is cited as an example. The document is a vendor's technical article whose latest survey data are from 2014; the numbers are specific examples and literature citations, not an independent measurement study.
Key points
- Uptime Institute 2014 survey: industry average PUE of 1.7 (1.67 in 2013, 1.8 in 2012).
- Power cost ranks second only to personnel in data-centre total cost of ownership.
- Barclays unplugged 9,124 unnecessary servers in 2013 and reduced its power bill by $4.5 million.
- With N+X or 2N redundancy, UPS load is often 30 to 40% or lower; full-load efficiency is unrealistic.
- In a 200 kVA example, a high-efficiency modular UPS (the legacy unit carries 4% extra losses at 50% daytime load and 7% at 30% night load) saves about 286,160 kWh over 8 years, or EUR 28,616 at 0.1 EUR/kWh (5%).
- An EPA study found effective hot and cold air containment cut fan power by 25% and chiller power by 20%.
- ASHRAE recommended range is 18 to 27 degrees C; per an Intel study each 1 degree C rise in ambient temperature cuts cooling cost by about 4%.
- A high-temperature chilled water system raises supply water temperature above the conventional 7 degrees C.
- Seven strategies: hardware audits, routine PUE measurement, server efficiency, cooling efficiency, higher temperature, DCIM and clean energy.
Using it in design
- When selecting UPS, look at the efficiency curve across the real load range (especially 20 to 40%) rather than full-load efficiency, and consider modular UPS to grow capacity with demand.
- Calculate the life-cycle cost of UPS efficiency differences (as in the example, over 8 years at a unit electricity cost) and include it in tender evaluation.
- Define sensors (kW and kVA) in design to monitor PUE year-round and report seasonal variation.
- Reflect hot and cold aisle containment, higher-temperature operation (ASHRAE 18 to 27 degrees C) and higher chilled-water temperature in cooling design.
- Add DCIM-based detection of idle servers and asset utilisation tracking to the operations plan.
Who should read it
Designers and operators seeking an introduction to data-centre energy efficiency strategy, and engineers evaluating UPS and cooling procurement.
Document contents
- Introduction
- Green data center strategy
- Strategy 1: Regular hardware audits
- Strategy 2: Routine PUE measurement
- Strategy 3: Upgrade hardware and improve server efficiency
- Strategy 4: Improving data center cooling efficiency
- Strategy 5: Increase data center temperature
- Strategy 6: Introduction of DCIM system
- Strategy 7: Use clean, renewable energy sources
- Conclusion
Publication details
- Authors
- Delta Power Solutions
- Publisher
- Delta Power Solutions
- Year
- Year not stated
- Document number
- WP0014_en-us
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Publisher landing page opened with TinyFish on 2026-11-16. No explicit open licence or commercial redistribution grant was displayed in the retrieved page; retained as metadata and original summary only. Free access or a download button is not permission to redistribute. Full publisher article opened. Search and page metadata report recent crawl/update dates but content cites 2013–2014 material; publication year intentionally omitted. License evidence: https://www.deltapowersolutions.com/en/mcis/white-paper-overview-of-green-energy-strategies-and-techniques-for-modern-data-centers.php
Citation
Delta Power Solutions Overview of Green Energy Strategies and Techniques for Modern Data Centers. Delta Power Solutions. WP0014_en-us. https://www.deltapowersolutions.com/en/mcis/white-paper-overview-of-green-energy-strategies-and-techniques-for-modern-data-centers.php
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
