White paperFree to read2020

Carbon Cutting in the Data Center

Riello UPS

Riello UPS's March 2020 white paper: it explains PUE and alternative metrics, and in a project raising UPS efficiency from 92% to 96% with a modular transformerless UPS, cooling cost falls 71.81% and annual carbon emissions 71.89%.

On this page

Overview

The white paper addresses the role of UPS efficiency in data-centre energy use and carbon footprint. The introduction, citing GeSI data, states that data centres consume about 3% of the energy produced worldwide and produce at least 2% of greenhouse gas emissions, that electricity can reach 25-60% of operating costs, and that a hyperscale data centre using 30 GWh a year pays about 3 million euros.

The measurement section defines PUE (total power over IT power) and lists its limits: it ignores climate differences, water used for cooling and renewable energy. Alternatives GPUE, DCIE, GUE and CUE are introduced; CUE is total CO2 emissions over IT energy and can also be found by multiplying annual PUE by the regional emission factor. The author says these metrics have not yet displaced PUE, which will stay the main metric.

The efficiency section favours modular UPS: older large systems reach optimum efficiency only when load is 80-90%, but are sized large for redundancy, so efficiency falls at low load. Modular design gives load-proportional installation, pay-as-you-grow scalability, hot-swapping, smaller and lighter units and, with a transformerless design (5% more efficiency than a conventional monoblock UPS), up to 96% efficiency even at 25% load. ECO mode can lift efficiency to 99% but exposes the critical load to mains fluctuations and so must be judged case by case. Li-ion batteries, demand-side response (DSR) and DCIM/EMS integration are named as further opportunities.

The example project replaces 2007-era 400 and 800 kVA static UPS (running at 12-25% load, average efficiency 92%, 89% in the main distribution room) in two data centres of a major consumer-goods supplier with a Riello Multi Power modular transformerless system. This is a manufacturer white paper; the customer is not named and the figures are the manufacturer's.

Key points

  1. Data centres consume about 3% of the energy produced worldwide and generate at least 2% of greenhouse gas emissions (GeSI).
  2. Electricity can be 25-60% of data-centre operating cost; a hyperscale site using 30 GWh a year pays about 3 million euros a year.
  3. PUE ignores climate, cooling water and renewable energy; CUE, GPUE, DCIE and GUE are alternatives but PUE remains the main metric.
  4. Older large UPS are most efficient at 80-90% load; modular design reduces oversizing.
  5. Transformerless modular UPS gain 5% more efficiency than conventional monoblock UPS and reach up to 96% at 25% load; ECO mode can reach 99%.
  6. Example project: 2007-era 400 and 800 kVA static UPS at 12-25% load, average efficiency 92% (89% in the distribution room); the new system raises efficiency from 92% to 96%.
  7. Result: annual carbon emissions at two sites fall 71.89% (2147 kg to 603.5 kg), air-conditioning cost falls 71.81% (297.3 kW, 226,000 euros), and cooling energy savings reach up to 1.25 million kWh.
  8. The new system takes less than half the former space; UPS footprint falls 59%.
  9. European data centres consume about 250 TWh a year.

Using it in design

  • In UPS selection base efficiency on the expected operating load, not full load; old large monoblock systems lose much efficiency at 12-25% load.
  • With modular UPS, consider installing to current load and expanding pay-as-you-grow.
  • If ECO mode is to be used, assess in a risk analysis that the critical load will be exposed to mains fluctuations; the mode may not be usable at every site.
  • Include the cooling effect of an efficiency gain (less UPS heat loss lowers air-conditioning load) in total energy and carbon calculations.
  • Add interfaces that integrate UPS monitoring with EMS and DCIM to the specification, and assess Li-ion batteries and demand-side response separately.
  • Add a carbon-focused metric such as CUE to the monitoring plan alongside PUE.

Who should read it

Operations managers, electrical designers and UPS replacement decision makers working on data-centre energy efficiency and carbon reduction targets.

Document contents

  1. Introduction
  2. How to measure data center efficiency
  3. Improving efficiency: modular UPS
  4. ECO mode, UPS monitoring and battery storage
  5. Practical example of efficiency and savings
  6. Conclusion

Related standards

  • ISO/IEC 30134-2
  • ISO/IEC 30134-8
  • IEC 62040-3

Publication details

Authors
Riello UPS
Publisher
Riello UPS
Year
2020
Document number
Whitepaper No. 03-2020
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Footer '© Riello UPS | All Rights Reserved'; free PDF.

Citation

Riello UPS (2020). Carbon Cutting in the Data Center. Riello UPS. Whitepaper No. 03-2020. https://www.riello-ups.com/uploads/file/774/2774/Riello_UPS_WhitePaper_DataCenter_03-20_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.