Deploying 800VDC Architectures for Large-Amperage Data Centers

Eaton · Steven Johnston, Alexandra Rangel-Santos et al.

Eaton's 2026 white paper (WP017005EN) on modular 800 V DC infrastructure, covering source fault behaviour, grounding, protection coordination, inrush and grid ride-through.

On this page

Overview

The white paper examines design issues for modular 800 V DC infrastructure in large-amperage data centres. The topics covered are source fault behaviour, grounding, protection coordination, inrush at energisation and grid ride-through. In DC distribution the fault current comes from power converters, so the protection approach built on high, sustained short-circuit current in AC systems does not apply directly.

The coordination discussion covers not only upstream breakers but also power converters and rack-level protective devices. For resistance-grounded systems, it states that pole-to-ground faults may require dedicated detection rather than conventional overcurrent detection.

Key points

  1. Subject: modular 800 V DC infrastructure and large-amperage data centres.
  2. Source fault behaviour, grounding, protection coordination, inrush and grid ride-through are covered.
  3. In resistance-grounded systems, pole-to-ground faults may require dedicated detection rather than conventional overcurrent detection.
  4. Protection coordination includes upstream breakers, power converters and rack-level protective devices together.

Using it in design

  • For 800 V DC distribution, choose the grounding method (for example resistance grounding) and define separate detection for pole-to-ground faults.
  • In the protection coordination study, include converter current limits and rack-level protective devices as well as breakers.
  • Set inrush at energisation and ride-through behaviour during grid faults as design criteria.
  • Take the source fault-current level from converter data and verify protective-device selection against it.

Who should read it

Electrical engineers designing 800 V DC data-centre distribution and those performing protection coordination.

Publication details

Authors
Steven Johnston; Alexandra Rangel-Santos; Anthony Parsons; Bruce Campbell; Swanand Jukevar; Xin Zhou; Brian Tureski; Jacob Chacko
Publisher
Eaton
Year
2026
Document number
WP017005EN
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer source inspected. No redistribution permission established. Metadata and original brief summaries only; local files are research evidence, not a redistribution package.

Citation

Steven Johnston; Alexandra Rangel-Santos; Anthony Parsons; Bruce Campbell; Swanand Jukevar; Xin Zhou; Brian Tureski; Jacob Chacko (2026). Deploying 800VDC Architectures for Large-Amperage Data Centers. Eaton. WP017005EN. https://www.eaton.com/content/dam/eaton/markets/data-center/the-impact-of-ai/whitepapers/eaton-deploying-800vdc-architecture-whitepaper-en-us.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.