UPS Installation Safety Requirements (Smart Tricks to Improve Power Supply Reliability series)
Eaton · Janne Paananen, Martijn Imming
Explains two frequently misunderstood UPS safety obligations under IEC 62040-1: backfeed protection and short-circuit withstand.
On this page
Overview
IEC 62040-1 requires backfeed isolation of a permanently connected UPS within 15 s after loss of supply; a static switch alone is not adequate isolation. The paper compares internal backfeed isolation with external input-line isolation. With external devices, warning labels are required on all switchgear access points between the UPS and the isolator, responsibility moves to the installer, and the arrangement may force a dual feed with separate rectifier and bypass supplies.
A single external backfeed contactor shared by several static switches turns one switch failure into loss of all bypass lines; internal contactors per module preserve redundancy and also isolate a shorted static switch.
IEC 62040-1:2008 Amendment 1:2013 became mandatory in February 2016: the manufacturer must declare a rated short-time withstand current (Icw) or a rated conditional short-circuit current (Icc) with a specified SCPD. Withstand testing is mandatory unless the declared Icw is 10 kA or less, or the SCPD limits peak let-through to 17 kA or less.
Each bypass circuit must be independently safe at the available fault level; paralleling UPSs does not reduce the requirement per unit. Generator-parallel-with-transformer cases and future upgrades must be considered.
Key points
- IEC 62040-1 requires backfeed isolation within 15 s after loss of supply for a permanently connected UPS; a static switch alone is not adequate.
- With external backfeed devices, warning labels are needed on all access points between UPS and isolator, responsibility moves to the installer, and a dual feed may be forced.
- One external contactor shared by several static switches loses all bypass lines on one switch failure; per-module internal contactors preserve redundancy.
- Amendment 1:2013, mandatory from February 2016: declare Icw or Icc with a specified SCPD.
- Withstand testing is mandatory unless declared Icw is 10 kA or less or the SCPD limits peak let-through to 17 kA or less.
- Each bypass circuit must be safe at the available fault level; paralleling does not reduce the per-unit requirement; generator paralleling and future upgrades must be considered.
Using it in design
- For UPS selection, record internal or external backfeed protection, Icw/Icc rating and the required SCPD.
- Compare the prospective fault current at the UPS bypass input (worst case, including generator paralleling and future transformer upgrades) with the declared rating.
- If backfeed protection is external, add an isolator and warning-label requirement to the switchboard schedule.
- Warn when one backfeed device serves several static switches.
Who should read it
Electrical engineers designing UPS inputs and switchboard schedules, and commissioning specialists.
Related standards
- IEC 62040-1:2008+A1:2013
- IEC 61439-1/2
Publication details
- Authors
- Janne Paananen; Martijn Imming
- Publisher
- Eaton
- Year
- 2018
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Janne Paananen; Martijn Imming (2018). UPS Installation Safety Requirements (Smart Tricks to Improve Power Supply Reliability series). Eaton. https://web.archive.org/web/20250701055009/https://www.eaton.com/content/dam/eaton/markets/data-center/documents/eaton-ups-installation-safety-requirements-white-paper-en-us.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.