Parallel UPS Systems
Eaton · Ed Spears
Eaton WP153026 explains how UPS modules are paralleled for capacity or N+1 redundancy: output synchronisation, load sharing, and centralised versus distributed bypass.
On this page
Overview
Paralleling is common: at least 50-60% of large UPS systems (300 kVA and up) are configured in parallel, and up to 40% of systems around 10 kVA. In the example, an 800 kVA load is protected by three 400 kVA modules in N+1, each carrying one third. In the N+1 alarm logic, five 100 kVA modules alarm when load exceeds 400 kVA.
The paper contrasts master-slave or communication-dependent paralleling schemes, which create single points of failure, with a peer-to-peer approach that needs no inter-module control wiring. Failure of the control system to switch to a redundant path is cited (GE) as the leading cause, 32%, of mission-critical power system failures.
Unbalanced load sharing (for example 40/40/20 in a three-module system) stresses some modules and can drive the system to bypass. When the paralleled modules together exceed one unit's internal static switch rating, a separate bypass cabinet with its own static switch is needed.
Parallel limits by range are given as examples: the 9395 at 200-1200 kVA up to 4800 kVA (N+1) and the 93PM at 20-400 kW up to 1200 kW. Tie cabinets are among the deployment considerations.
Key points
- At least 50-60% of large UPS systems (300 kVA and up) are paralleled; up to 40% of ~10 kVA systems.
- Example: an 800 kVA load on three 400 kVA modules in N+1, each carrying one third.
- Combined modules above one unit's internal static switch rating need a separate bypass cabinet.
- Control-system failure to switch to a redundant path is cited as the leading cause (32%, GE) of mission-critical power failures.
- Unbalanced sharing such as 40/40/20 stresses some modules and can drive the system to bypass.
- N+1 alarm: five 100 kVA modules alarm when load exceeds 400 kVA.
- Parallel limits: 9395 200-1200 kVA up to 4800 kVA (N+1); 93PM 20-400 kW up to 1200 kW.
Using it in design
- For UPS selection, record maximum parallel units, distributed or centralised bypass architecture and static switch rating.
- Compute redundancy-aware capacity (N+1 usable = (n-1) x module rating) and alert when design load exceeds it.
- Require external bypass cabinet sizing when the combined output exceeds a single static switch rating.
- Warn when the parallel scheme relies on a single master controller.
Who should read it
Electrical designers choosing a paralleled UPS arrangement for capacity or N+1.
Related standards
- IEC 62040-3
Publication details
- Authors
- Ed Spears
- Publisher
- Eaton
- Year
- 2020
- Document number
- WP153026EN
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Ed Spears (2020). Parallel UPS Systems. Eaton. WP153026EN. https://web.archive.org/web/20231018175350/https://www.eaton.com/content/dam/eaton/products/backup-power-ups-surge-it-power-distribution/backup-power-ups/power-xpert-9395/eaton-ups-parallel-whitepaper-wp153026en.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.