The price of a degree-hour in data-centre cooling: Auditing deep reinforcement learning against model predictive control
Energy and AI (Elsevier BV) · Yared Brhane Tadese, Raman Barnwal et al.
A 2026 Energy and AI paper that audits deep reinforcement learning claims in kWh per degree-hour: the benchmark default is 10 kWh, metered plants pay 0.73-1.22 kWh; none of 102 policies held the band, while tuned MPC held it in three of six environments.
On this page
Overview
The paper exposes the price that deep reinforcement learning (DRL) benchmarks for data centre cooling implicitly put on thermal-band violation, expressed as kWh per degree-hour. This price is compared with values in public benchmarks and with metered tropical plants. It is published in Energy and AI (Elsevier).
The study also tests PPO and SAC policies against tuned feedback and model predictive control (MPC) controllers. The data-centre benchmark default charges 10 kWh per degree-hour of violation, while metered plants pay 0.73 to 1.22 kWh (1.3 to 23.5 when scaled to the simulated hall). None of 102 policies trained on the first benchmark held the recommended thermal band; tuned MPC held the band exactly in three of six environments.
Key points
- The data-centre benchmark default charges 10 kWh per degree-hour of band violation.
- Metered plants pay 0.73-1.22 kWh per degree-hour; 1.3-23.5 when scaled to the simulated hall.
- None of 102 policies trained on the first benchmark held the recommended thermal band.
- Tuned MPC held the band exactly in three of six environments.
- PPO and SAC policies are compared with tuned feedback and MPC controllers.
Using it in design
- When assessing AI control proposals for cooling optimisation, compare penalty weights (kWh per degree-hour) with metered plant data.
- Before commissioning a new DRL controller, compare it with tuned feedback and MPC baselines.
- Define thermal band violation as an acceptance criterion and test that the control algorithm holds it.
- When scaling benchmark results to your own hall, recompute the implied band price.
Who should read it
Engineers and researchers evaluating data centre cooling control and AI-based optimisation.
Related standards
- ASHRAE TC 9.9 thermal guidelines
Publication details
- Authors
- Yared Brhane Tadese; Raman Barnwal; Bibek Dhakal; Manohar Chamana; Olatunji Adeyanju; Stephen Bayne; Argenis Bilbao
- Publisher
- Energy and AI (Elsevier BV)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Crossref says CC BY but OpenAlex lists CC BY-NC-ND; kept non-redistributable until checked manually.
Citation
Yared Brhane Tadese; Raman Barnwal; Bibek Dhakal; Manohar Chamana; Olatunji Adeyanju; Stephen Bayne; Argenis Bilbao (2026). The price of a degree-hour in data-centre cooling: Auditing deep reinforcement learning against model predictive control. Energy and AI (Elsevier BV). https://doi.org/10.1016/j.egyai.2026.100936
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.