Comparative analysis of scenarios of data center waste heat utilization for district heating networks of different generations
Energy Conversion and Management (Elsevier BV) · D. Romanov, I. Chakraborty et al.
A 2025 Energy Conversion and Management study compares waste-heat recovery and borehole storage for a Göttingen campus; average marginal waste heat prices range from 48 to 93 EUR/MWh.
On this page
Overview
The study compares three scenarios under district heating (DH) temperatures representing different network generations: business as usual (BAU), data-centre waste heat recovery (WH), and WH complemented by a shallow borehole thermal energy storage that addresses the mismatch between heat demand and waste heat production (WH + BTES). The Göttingen north campus is the case study.
The analysis uses a customised Python model that incorporates the pygfunction package and a regression-based heat pump model. The WH scenario covers about 70% of the considered heating and cooling demand, and WH+BTES adds about 20%. WH is currently the most economic scenario, while WH+BTES allows higher CO2 savings.
Sensitivity analysis indicates that storing waste heat could become economic if BTES capital cost fell by 35% and the ratio of DH price to electricity price rose to 2.5 times the current value. Monte Carlo simulation gives marginal waste heat prices for WH, averaging 48, 56, 90 and 93 EUR/MWh for DH design supply temperatures of 120, 95, 70 and 48 °C respectively.
Key points
- The WH scenario covers about 70% of the considered heating and cooling demand; WH+BTES adds about 20%.
- WH alone is currently the most economic scenario; BTES gives higher CO2 savings.
- BTES becomes economic if its capital cost falls 35% and the DH-to-electricity price ratio reaches 2.5 times today's.
- Average marginal waste heat prices are 48, 56, 90 and 93 EUR/MWh for DH supply temperatures of 120, 95, 70 and 48 °C.
- Low-temperature DH operators can expect larger profits if waste heat prices are constant across network temperatures.
Using it in design
- In heat export feasibility, take the DH supply temperature as the basic input for heat pump lift and waste heat value.
- For the seasonal mismatch between heat demand and waste heat output, evaluate storage such as BTES with capital cost and price ratio sensitivity.
- Test the economic effect of differentiating the heat price by network temperature using the Monte Carlo range.
Who should read it
Data-centre designers planning heat export, district heating operators and energy economics analysts.
Publication details
- Authors
- D. Romanov; I. Chakraborty; S. Holler
- Publisher
- Energy Conversion and Management (Elsevier BV)
- Year
- 2025
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
D. Romanov; I. Chakraborty; S. Holler (2025). Comparative analysis of scenarios of data center waste heat utilization for district heating networks of different generations. Energy Conversion and Management (Elsevier BV). https://doi.org/10.1016/j.enconman.2025.119856
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.