Enhancing third-generation district heating networks with data centre waste heat recovery: analysis of a case study in Italy
Energy (Elsevier BV) · Luca Socci, Andrea Rocchetti et al.
A 2024 Energy study integrates the waste heat of a 100-500 kW data centre into an Italian third-generation district heating network using high-temperature heat pumps, cutting gas consumption by 11-58%.
On this page
Overview
The study evaluates integrating data-centre waste heat into a third-generation district heating network that is currently supplied by natural-gas-fired combined heat and power devices. The data centre is a source of low-grade thermal waste heat, which is upgraded to the temperature the network requires using high-temperature heat pumps.
Energy analyses are conducted on an hourly basis, using network load profiles derived from a real case study and varying data-centre thermal loads of 100-500 kW. In the integrated configuration the data-centre cooling system discharges its heat into the network.
A non-integrated 100 kW data centre produces 926 MWh/year of waste heat that is discharged to the environment, contributing to the urban heat island effect. In the integrated scenarios the waste heat share of the network energy mix ranges from 12% to 59%, and gas consumption falls by 11% to 58%.
Key points
- A non-integrated 100 kW data centre produces 926 MWh/year of waste heat, which is discharged to the environment.
- In integrated scenarios the waste heat share of the network energy mix ranges from 12% to 59%.
- Gas consumption reductions range from 11% to 58% (12-59% in the paper's highlights).
- Data-centre thermal load is varied from 100 to 500 kW in an hourly analysis.
- Waste heat is upgraded to third-generation network temperature with high-temperature heat pumps.
Using it in design
- Calculate the waste heat potential of a small or mid-size facility with an hourly load profile and overlay it on the network's heat demand profile.
- Include high-temperature heat pump selection and electricity use for the third-generation network temperature in the heat export cost.
- Base the emissions gain on the fossil fuel (gas cogeneration) that the waste heat would displace.
Who should read it
Designers planning heat export from small and mid-size data centres, and district heating engineers.
Publication details
- Authors
- Luca Socci; Andrea Rocchetti; Antonio Verzino; Andrea Zini; Lorenzo Talluri
- Publisher
- Energy (Elsevier BV)
- Year
- 2024
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Luca Socci; Andrea Rocchetti; Antonio Verzino; Andrea Zini; Lorenzo Talluri (2024). Enhancing third-generation district heating networks with data centre waste heat recovery: analysis of a case study in Italy. Energy (Elsevier BV). https://doi.org/10.1016/j.energy.2024.134013
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
