Small-signal stability of DC microgrid under data center load: Theoretical analysis and experimental validation
International Journal of Electrical Power & Energy Systems (Elsevier BV) · Qihao Guo, Jérôme Buire et al.
An experimentally validated study of DC microgrid small-signal stability under data-centre load, using eigenvalue and impedance methods and taking the load's negative incremental impedance and AI-driven power fluctuations into account.
On this page
Overview
The study aims to improve the small-signal stability of a DC microgrid operating under data-centre load profiles. A basic one-source, one-cable, one-load DC microgrid captures all destabilizing elements without adding unnecessary complexity. The dynamic behaviour of the data-centre load is investigated in detail, with a focus on its negative incremental impedance and the severe power fluctuations induced by AI model execution.
Two complementary analysis methods are used. Eigenvalue analysis highlights the adverse effects of control interference and improper system parameter design. An impedance-based stability analysis relying solely on terminal measurements is also performed, and both methods are shown to determine system stability effectively. The accuracy is validated on an experimental testbed built with imperix rapid control prototyping solutions.
Two stability enhancement solutions are proposed that damp the poorly damped oscillatory mode without changing the control structure. Finally, the framework is extended to a multi-converter DC microgrid configuration, demonstrating the scalability of the proposed stability analysis.
Key points
- The data-centre load shows negative incremental impedance and severe power fluctuations induced by AI execution.
- Eigenvalue analysis reveals the effect of control interference and poor parameter design on stability.
- Impedance-based analysis relying only on terminal measurements also predicts stability correctly.
- The analysis is validated on an experimental testbed built with imperix rapid control prototyping solutions.
- Two solutions damp the poorly damped oscillatory mode without changing the control structure.
- The framework is extended to multi-converter DC microgrids.
Using it in design
- In DC-distributed data centres, define the load as a constant-power load with negative incremental impedance and check stability together with cable and source-converter parameters.
- When selecting control parameters, use eigenvalue results to identify control interference and poorly damped modes in advance.
- Add impedance measurement to the commissioning plan so that terminal-measurement impedance verification is possible.
- On multi-converter DC buses, reassess stability separately from single-converter operation.
Who should read it
Power-electronics and electrical engineers designing DC-distributed data centres and microgrids.
Publication details
- Authors
- Qihao Guo; Jérôme Buire; David Frey; William Norris; Patrick Chambon
- Publisher
- International Journal of Electrical Power & Energy Systems (Elsevier BV)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Qihao Guo; Jérôme Buire; David Frey; William Norris; Patrick Chambon (2026). Small-signal stability of DC microgrid under data center load: Theoretical analysis and experimental validation. International Journal of Electrical Power & Energy Systems (Elsevier BV). https://doi.org/10.1016/j.ijepes.2026.112112
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.