Enel ST3 series three-phase static transfer switch technical specifications
Original title ST3 Serisi teknik özellikler
Enel
Enel's ST3 series three-phase static transfer switch (STS): twelve current ratings from 50 to 2500 A, transfer time <=5 ms for synchronous and <=10 ms for asynchronous sources, efficiency >=99%.
On this page
Overview
The one-page specification table presents Enel's ST3 series of three-phase static transfer switches. The series comes in twelve current ratings: 50, 100, 200, 250, 300, 400, 630, 800, 1000, 1200, 1500 and 2500 A, with 3 or 4 poles. Input voltage is 380-400-415 V, 3-phase plus neutral; the input voltage window is +/-25% and the frequency window +/-10%, both adjustable, with a rated frequency of 50/60 Hz.
Transfer uses break-before-make switching, with no short circuit between the sources. Transfer time is <=5 ms between synchronous sources and <=10 ms between asynchronous ones; transfer can be automatic or manual. Crest factor is 3.5:1.
Overload capacity is given as 60 min at 110%, 10 min at 130%, 2 min and 1 min at 150%, 10 s and 2 s at 200%, and 250 ms and 100 ms at 500%. Protections are overload, SCR fault detection, electronic short circuit and phase-sequence error. Switching is three-phase and control is microprocessor-based. UPS compatibility is stated for the C, D and E series.
General data: efficiency >=99%, forced-air cooling, optional remote monitoring panel. Operating temperature 0-40 °C, storage -10 to +50 °C, relative humidity 0-95% non-condensing, altitude <=2000 m, noise in four steps of <50, <55, <60 and <70 dB(A). Protection is IP20 and colour RAL9005. Safety is EN 62310-1, EMC EN 62310-2, and service life is 10 years.
Key points
- Twelve current ratings: 50, 100, 200, 250, 300, 400, 630, 800, 1000, 1200, 1500 and 2500 A; 3 or 4 poles.
- Input 380-400-415 V 3-phase + N; voltage window +/-25%, frequency window +/-10% (adjustable).
- Transfer time <=5 ms (synchronous sources), <=10 ms (asynchronous); break before make.
- Overload: 110% 60 min, 130% 10 min, 150% 2 min/1 min, 200% 10 s/2 s, 500% 250/100 ms.
- Crest factor 3.5:1; efficiency >=99%; forced-air cooling.
- Protections: overload, SCR fault detection, electronic short circuit, phase-sequence error.
- Operation 0-40 °C, humidity 0-95%, altitude <=2000 m; IP20.
- Standards EN 62310-1 and EN 62310-2; service life 10 years.
Using it in design
- In a dual-source feed, select the STS current rating against the load current and the 110% / 60 min overload limit, using the next higher rating step.
- If the sources are not synchronous (for example UPS and generator), compare the <=10 ms transfer time with the load ride-through.
- For downstream protection selectivity, assess the 250 ms (and 100 ms) limit at 500% together with breaker curves.
- In the electrical room layout, allow for forced-air cooling, IP20 and the 2000 m altitude limit.
- With a 10-year service life, include a renewal plan in the operating budget.
Who should read it
Electrical engineers designing dual-source power distribution, data-centre operators and UPS integrators selecting STS equipment.
Document contents
- Voltage (input, frequency, poles, crest factor)
- Transfer (mode, time, methods)
- Overload capacity
- General (protection, control, UPS compatibility, efficiency, cooling)
- Environment
- Physical characteristics
- Standards
- Service life
Publication details
- Authors
- Enel
- Publisher
- Enel
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Enel ST3 Serisi teknik özellikler. Enel. https://enel.com.tr/wp-content/uploads/2019/11/ST3-Serisi-1b.jpg
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.