Research paperPDF2026

Numerical Study on Effect of Ventilation on Fire Characteristics of Lithium-Ion Battery in Energy Storage Cabin

Batteries (MDPI AG) · Wei Lin, Lingcheng Zeng et al.

Using FDS, this study models single-cell thermal runaway in a roughly 100 kWh commercial storage cabinet of 280 Ah LFP cells and compares a closed cabinet with one that has an open top for temperature, CO and H2 fields.

CC BY 4.0: share with attribution

On this page

Overview

The study asks how much a designed venting path reduces heat and gas build-up in a storage cabinet during thermal runaway. A Fire Dynamics Simulator (FDS) model of a 1450.7 × 1100 × 1923 mm cabinet with five vertically stacked packs was built, with heat-release and gas-composition inputs from earlier experiments. Runaway was triggered at a critical cell temperature of 180 °C, and a 50 mm grid was chosen after a 100/50/25 mm grid-independence study. A fully closed cabinet and one with an open top were compared over a 100 s window.

In the closed cabinet, local peak temperature exceeded 700 °C and CO and H2 reached around 1000 ppm within 60 s after runaway onset, still rising at the end of the window. H2 rose quickly and formed a growing flammable layer under the roof. The explosion concentration limit of LFP vent gas is cited as 4-15% depending on SOC, with H2 and CO the main contributors, and LFP vent gas has been ignited below the theoretical LEL in confined, non-uniform mixtures.

In the open-top cabinet, an unobstructed buoyancy-driven venting channel formed, and peak temperature and peak CO and H2 concentrations at side monitoring points fell by more than 80% compared with the closed cabinet. Commercial and industrial storage cabinets typically hold 100-215 kWh each.

Limits: the study is simulation-only, battery blocks are homogenised and only a single-cell runaway is modelled; propagation, explosion and vent or door opening details in a real cabinet are not tested. It is useful mainly to show the order-of-magnitude effect of designed venting.

Key points

  1. Commercial and industrial storage cabinets typically hold 100-215 kWh each; the modelled cabinet is 1450.7 × 1100 × 1923 mm with five vertically stacked packs.
  2. The explosion concentration limit of LFP vent gas is cited as 4-15% depending on SOC, with H2 and CO the main contributors; ignition below the theoretical LEL has been reported in confined, non-uniform mixtures.
  3. Runaway was triggered at a critical cell temperature of 180 °C; a 50 mm FDS grid was chosen after a 100/50/25 mm grid-independence study.
  4. In the fully closed cabinet, local peak temperature exceeded 700 °C and CO and H2 reached around 1000 ppm within 60 s after runaway onset, still rising at the end of the 100 s window.
  5. H2 rose quickly and formed a growing flammable layer under the roof of the closed cabinet.
  6. With an open top, peak temperature and peak CO and H2 concentrations at side monitoring points fell by more than 80% compared with the closed cabinet.

Using it in design

  • Define a designed, buoyancy-driven vent or relief path at the top of a storage cabinet; in a closed cabinet H2 forms a flammable layer under the roof, so control gas and heat build-up.
  • Consider placing gas detectors near the cabinet ceiling, where H2 accumulates, and link detection alarms with ventilation and explosion-protection logic.
  • Knowing the homogenised-block, single-cell assumption of this study, use the results as an order-of-magnitude effect and ask for testing and explosion-relief analysis for the real cabinet.

Who should read it

Engineers designing ventilation and explosion protection for commercial and industrial battery cabinets and BESS containers.

Document contents

  1. 1. Introduction
  2. 2. Model Description (2.1 Physical Model and Locations of Detectors, 2.2 Governing Equations, 2.3 Boundary Conditions, 2.4 Grid Analysis)
  3. 3. Results and Analysis (3.1 Fire Spread Behavior in Closed Cabin: fire propagation characteristics, gas dispersion analysis; 3.2 Fire Spread Behavior in Cabin Without Top Cover)
  4. 4. Conclusions

Related standards

  • NFPA 855
  • NFPA 68
  • NFPA 69
  • UL 9540A

Read the document

energy-storage-cabin-ventilation-fire-2026.pdf

PDF · 23.5 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Wei Lin; Lingcheng Zeng; Junyu Liu; Zhiying Ding
Publisher
Batteries (MDPI AG)
Year
2026
Volume
12
Issue
7
Pages
250
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
www.mdpi.com
Original licence note

PDF p.1 states the article is distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.

Citation

Wei Lin; Lingcheng Zeng; Junyu Liu; Zhiying Ding (2026). Numerical Study on Effect of Ventilation on Fire Characteristics of Lithium-Ion Battery in Energy Storage Cabin. Batteries (MDPI AG). 12(7), 250. https://doi.org/10.3390/batteries12070250

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.