Technical guideFree to read2026

ENERGY STAR Certified Uninterruptible Power Supplies

U.S. Environmental Protection Agency

The U.S. Environmental Protection Agency's public registry of certified UPS models with rated active and apparent output power, tested configurations and efficiencies at individual load points. It is a traceable supplement to manufacturer datasheets. Qualification is not a statement of current product availability.

On this page

Overview

The dataset lists models that meet all requirements of the ENERGY STAR UPS Program Requirements Version 2.0, effective 1 January 2019. All records are AC-output, static power conversion units; the snapshot examined holds 923 records. Records have 102 columns: model identity and description, product and topology type, application, rated input and output voltage and frequency, physical dimensions and rack mounting, number of outlets, normal-mode input dependency class, test conditions, efficiency at load points, power factor, energy storage characteristics, communication protocols, take-back programme and market information.

The topology breakdown is: double conversion 155, multi-mode double conversion 351, line interactive 292, multi-mode line interactive 6, passive standby 96 and other 23. 802 records are non-modular and 121 are modular UPS; 520 are single-normal-mode and 403 are multiple-normal-mode units. By application, some models are consumer only, some commercial only, 49 data centre only, and the others span several applications. Minimum-configuration apparent output power runs from 240 VA to 1,000,000 VA.

AC UPS rows distinguish minimum and maximum tested configurations and carry lowest and highest input-dependency efficiency columns; modular UPSs have the maximum configuration tested separately. Normal-mode input-dependency classes are defined as VFD (voltage and frequency dependent), VI (voltage independent) and VFI (voltage and frequency independent). For multiple-normal-mode units the default normal mode is the one in the as-shipped configuration. Efficiency is given at 25%, 50%, 75% and 100% load and as a weighted average, with total input power at 0% load in a separate column. These contexts must stay attached to an imported curve.

The dataset is useful for comparing products but has limits: the data rests on the manufacturer's certification submission and does not show sales status; consumer and commercial models under ENERGY STAR sit in the same table as data-centre-scale models, and the efficiency of low-power units cannot be compared directly with large systems. In use, the normal mode and the input-dependency column each model was tested under should be preserved.

Key points

  1. The dataset covers certified models meeting ENERGY STAR UPS Program Requirements Version 2.0 (effective 1 January 2019); all records are AC-output static UPSs.
  2. The snapshot examined holds 923 records and 102 columns.
  3. Topology breakdown: multi-mode double conversion 351, line interactive 292, double conversion 155, passive standby 96, other 23, multi-mode line interactive 6.
  4. 802 records are non-modular and 121 are modular UPS; 520 are single-normal-mode and 403 are multiple-normal-mode.
  5. Minimum-configuration apparent output power ranges from 240 VA to 1,000,000 VA.
  6. AC UPS rows separate minimum and maximum tested configurations and lowest and highest input-dependency efficiency columns; these contexts must stay attached to the curve.
  7. Efficiency is given at 25%, 50%, 75% and 100% load and as a weighted average; input power at 0% load and input power factor are separate columns.
  8. Normal-mode input dependency is classed as VFD, VI or VFI; for multiple-normal-mode units the default mode is stated separately.
  9. Qualification is not a statement of current product availability.

Using it in design

  • In UPS selection, filter data-centre-scale models and cross-check the efficiency curve (25%, 50%, 75% and 100% load) against the manufacturer datasheet; use the point in your design load range rather than a single weighted value.
  • For multiple-normal-mode units, record which normal mode (VFI, VFD) and which input-dependency column an efficiency value came from; assess the protection level of the high-efficiency mode (VFD) separately.
  • For modular UPSs, keep the minimum and maximum configuration results apart and compare according to which configuration your design load is closer to.
  • In PUE and loss calculations, enter UPS efficiency by load percentage; add input power at 0% load as no-load loss.
  • Confirm separately with the manufacturer whether a model is currently on sale; the certification record does not give that information.

Who should read it

Electrical designers selecting UPSs, energy-efficiency analysts, and teams building catalogues and data models.

Document contents

  1. Dataset description and programme requirements
  2. Model identity and product information (brand, model, product and topology type, application)
  3. Rated power and configuration information (active and apparent output power, minimum and maximum configuration)
  4. Input and output ratings and normal-mode input dependency
  5. Efficiency and power factor (load points, weighted efficiency, input power at 0% load)
  6. Energy storage, communication and market information

Publication details

Authors
U.S. Environmental Protection Agency
Publisher
U.S. Environmental Protection Agency
Year
2026
Document number
Socrata ifxy-2uty
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

U.S. Environmental Protection Agency (2026). ENERGY STAR Certified Uninterruptible Power Supplies. U.S. Environmental Protection Agency. Socrata ifxy-2uty. https://data.energystar.gov/Active-Specifications/ENERGY-STAR-Certified-Uninterruptible-Power-Suppli/ifxy-2uty

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.