Uninterruptible Power Supplies Key Product Criteria

ENERGY STAR · U.S. Environmental Protection Agency

The ENERGY STAR page summarising UPS Version 2.0 for AC-output units operating in a single input dependency: the load-weighted average efficiency formula, loading assumptions, minimum efficiency equations and VFD, VI and VFI class definitions.

On this page

Overview

The specification sets minimum average efficiencies for UPS units by input dependency (VFD, VI, VFI) and rated output power, with different rules from units up to 1500 W to those above 10,000 W. The criteria on the page are for AC-output UPS units that operate in a single input dependency; multi-mode systems (for example VFD and VFI) and DC-output UPS/rectifiers used in telecommunications have additional criteria in sections 3.2.2-3.2.3 and 3.3 of the Version 2.0 requirements.

Average efficiency is EffAVG = t25% x Eff25% + t50% x Eff50% + t75% x Eff75% + t100% x Eff100%, where t is the proportion of time at that percentage of the reference test load and Eff is efficiency measured by the ENERGY STAR test method. The Table 1 weights vary with power and class: up to 1500 W, VFD 0.2/0.2/0.3/0.3 and VI and VFI 0/0.3/0.4/0.3; from 1500 to 10,000 W all classes 0/0.3/0.4/0.3; above 10,000 W all classes 0.25/0.5/0.25/0. So above 10 kW the 25, 50 and 75 percent load points are used and the 100 percent point gets no weight.

Table 2 gives the minimum average efficiency. Below 350 W: VFD 5.71 x 10^-5 x P + 0.962, VI 5.71 x 10^-5 x P + 0.964, VFI 0.011 x ln(P) + 0.824. From 350 to 1500 W: VFD 0.982, VI 0.984. From 1500 to 10,000 W: VFD 0.981 - EMOD, VI 0.980 - EMOD, VFI 0.0145 x ln(P) + 0.800 - EMOD (EMOD = 0.004 for modular UPS). Above 10,000 W: VFD 0.97, VI 0.94, VFI 0.0058 x ln(P) + 0.886. The requirement is rounded to the third decimal. All AC-output VI and VFI UPS units must also reach a power factor of at least 90 percent at 100 percent load.

The page defines three input dependencies: VFD (passive, offline, standby), typically up to 1500 VA for small offices and homes; VI (line-interactive), typically up to 5000 VA for small business and departmental servers, with multi-tap autotransformers; and VFI (online, double conversion), typically up to 1000 kVA and used in data centres, giving continuous supply with no transfer time.

Key points

  1. Average efficiency: EffAVG = t25% x Eff25% + t50% x Eff50% + t75% x Eff75% + t100% x Eff100% (t values from Table 1).
  2. For AC UPS above 10 kW the weights at 25%, 50% and 75% load are 0.25, 0.50 and 0.25; the 100% point gets zero weight.
  3. Up to 1500 W: VFD weights 0.2/0.2/0.3/0.3; VI and VFI 0/0.3/0.4/0.3.
  4. From 1500 to 10,000 W all classes use weights 0/0.3/0.4/0.3.
  5. Minimum average efficiency above 10 kW: VFD 0.97, VI 0.94, VFI 0.0058 x ln(P) + 0.886.
  6. Minimum average efficiency from 350 to 1500 W: VFD 0.982, VI 0.984.
  7. For modular UPS in the 1500-10,000 W range an EMOD allowance of 0.004 applies.
  8. All AC-output VI and VFI UPS must have a power factor of at least 90 percent at 100 percent load.
  9. Multiple-mode AC systems and DC rectifiers have additional requirements; single-mode criteria do not cover every operating case.

Using it in design

  • Compare candidate UPS efficiency not only at full load but at the 25/50/75 percent points using the ENERGY STAR weights.
  • For UPS above 10 kW, do not make 100 percent load efficiency the selection criterion; the weighted average uses the 25-75 percent points.
  • Require a power factor of at least 0.9 at 100 percent load for VI and VFI units in the specification.
  • If multi-mode (eco) operation is planned, note that single-mode criteria are not enough and the additional Version 2.0 sections apply.
  • Choose the UPS class (VFD, VI, VFI) by load criticality: VFI for data centres.

Who should read it

Electrical designers setting UPS efficiency requirements and buyers of certified products.

Document contents

  1. Calculation of average efficiency for AC-output UPS
  2. Table 1: loading assumptions
  3. Table 2: minimum average efficiency requirement
  4. Information about input dependency characteristics (VFD, VI, VFI)

Publication details

Authors
U.S. Environmental Protection Agency
Publisher
ENERGY STAR
Year
2019
Document number
UPS Version 2.0 criteria
Document language
English
Source type
Expert / community
Access
Free to read
Licence
U.S. public domain: U.S. Government work; free to reuse
Licence evidence
www.copyright.gov
Original licence note

Published by a U.S. federal agency; works of the U.S. Government are not protected by copyright (17 U.S.C. 105).

Citation

U.S. Environmental Protection Agency (2019). Uninterruptible Power Supplies Key Product Criteria. ENERGY STAR. UPS Version 2.0 criteria. https://www.energystar.gov/products/uninterruptible_power_supplies/key_product_criteria

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.