Technical guideFree to readYear not stated

Akım Transformatörlerinin Gücü Nasıl Belirlenir?

Federal Elektrik

A Turkish-language technical library article from Federal Elektrik on how to choose the secondary rating of a current transformer: the burden needed is the sum of connected instrument demand, lead loss and about 0.5 VA of contact loss; in the example with two meters and 4 m of 2.5 mm² cable the burden is 3.93 VA and a 5 VA transformer is sufficient.

On this page

Overview

The article defines a current transformer as the component that reduces line current to a level that instruments, meters and relays can measure without damage and isolates those devices from high current. One point to watch in selection is secondary power: the transformer's rated burden has to cover the total demand of the connected devices. The practical calculation adds three components: device demand, connection cable losses and contact losses. The article gives data for each of the three and closes with a numerical example.

Device demands are tabulated as ranges: moving-iron ammeter 0.7 to 1.5 VA, wattmeter 0.2 to 5 VA, active and reactive energy meters 0.4 to 1 VA, reactive power control relay 0.5 to 1 VA, overcurrent relay 0.2 to 6 VA. For lead loss a second table lists the loss in VA of copper cable at 5 A secondary current for lengths of 1 to 10 m and cross-sections of 2.5 to 10 mm². The same value follows from P = (Isn² x 2L) / (S x 56), where L is the one-way cable length in metres and S the cross-section in mm².

Contact losses are taken as about 0.5 VA, depending on the number of connections between the secondary terminals and the devices. The example adds one active and one reactive meter (1 VA + 1 VA), 4 m of 2.5 mm² cable (1.43 VA) and contact loss (0.5 VA) to reach 3.93 VA. The article also points to an important lower bound: the demand must not exceed the transformer's rated burden nor fall below a quarter of it, otherwise measurement is inaccurate and protection signals are wrong. The final part summarises the manufacturer's range from 30 A to 4000 A.

Key points

  1. Secondary burden = device demand + connection cable losses + contact losses.
  2. Typical device burdens: meters 0.4 to 1 VA, ammeter 0.7 to 1.5 VA, wattmeter 0.2 to 5 VA, power factor meter 2 to 6 VA, overcurrent relay 0.2 to 6 VA, secondary thermal relay 7.2 to 9 VA.
  3. Lead loss relation: P = (Isn² x 2L) / (S x 56) VA; about 0.36 VA per metre for 2.5 mm² copper at 5 A secondary current.
  4. Loss over 10 m at 5 A secondary: 3.57 VA for 2.5 mm², 2.24 VA for 4 mm², 1.49 VA for 6 mm², 0.89 VA for 10 mm².
  5. Contact losses are taken as about 0.5 VA.
  6. Example: 1 VA + 1 VA + 1.43 VA + 0.5 VA = 3.93 VA; a transformer with 5 VA secondary rating is sufficient.
  7. The connected burden must not exceed the rated burden and must not fall below a quarter of it.
  8. The manufacturer's range: rated current 30 A to 4000 A, rated burden 2.5 VA to 40 VA, accuracy classes 0.2, 0.2s, 0.5 and 0.5s; standard secondary current 5 A, 1 A on request.

Using it in design

  • Draw up a burden budget for every metering point: power analyser or meter demand, lead loss and the 0.5 VA contact allowance.
  • Where the analyser is remote from the switchboard, calculate lead loss with the relation; for long runs increase the cross-section or choose a 1 A secondary, which cuts the loss by a factor of 25.
  • Choose a rated burden above the calculated load but such that the load stays above a quarter of the rating; with low-demand digital analysers an oversized VA rating degrades accuracy.
  • At points used for billing and PUE measurement, write the accuracy class (0.2s or 0.5s) into the specification together with the burden budget.
  • During commissioning, compare secondary circuit length and cross-section with the design; site changes alter the burden.

Who should read it

Electrical engineers designing metering and energy monitoring circuits, panel builders, and commissioning teams.

Document contents

  1. Akım transformatörlerinin gücü nasıl belirlenir?
  2. Akım transformatörlerine bağlanan bazı cihazların güçleri
  3. Bakır kablolardan ileri gelen ilave yükler
  4. Kablonun güç kaybı hesabı
  5. Temas kayıpları

Publication details

Authors
Federal Elektrik
Publisher
Federal Elektrik
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.

Citation

Federal Elektrik Akım Transformatörlerinin Gücü Nasıl Belirlenir?. Federal Elektrik. https://federalelektrik.com/teknik-kutuphane/akim-transformatorlerinin-gucu-nasil-belirlenir

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.