Technical guideFree to readYear not stated

TPM-05 and TPM-05A Energy Analyzer User Manual

Original title TPM-05 and TPM-05A: User Manual

Tense Electric Electronics

The Tense Electric Electronics TPM-05 and TPM-05A energy analyzer manual (DK-070-6) covers measurement up to the 41st harmonic, RS485 Modbus RTU, two relay outputs and event logging; the TPM-05A measures neutral current through a separate CT.

On this page

Overview

The TPM-05 and TPM-05A, made in Turkey, are energy analyzers for panels with 3P4W connection. The manual says they measure voltage and current harmonics up to the 41st (phase-neutral and phase-phase) and display active, reactive and apparent power per phase and in total, power factor and cos phi, import and export active energy, inductive and capacitive reactive energy, demand values, and minimum, maximum and average voltage and current. The display is a 71.5 x 61.5 mm glass LCD, communication is RS485 Modbus RTU, outputs are two adjustable relays and one digital input, and supply is 85-240 VAC 50/60 Hz at under 6 VA.

For current transformer selection the manual advises that the CT rating exceed the maximum current drawn, that the class be 0.5, that CT output cables be kept away from high-voltage lines and that CTs be fixed to bar, cable or rail. On the TPM-05A the neutral current is measured through a separate neutral CT; the display shows the real neutral current, the vector sum of phase currents and the scalar sum on three lines. Installation calls for 5 cm clearance behind the device, a switch or circuit breaker in the panel and cables complying with IEC 60227 or IEC 60245.

At first start-up the CT ratio is entered first, and the voltage transformer ratio if medium voltage is measured. For a 100/5 A CT the multiplier is 20 and CTR is set to 0020; for a VT converting 34,500 V to 110 V the ratio is 34,500/110 = 313.6. CTR ranges from 1 to 5000 and VTR from 1.0 to 999.9. Baud rate is 1200-115200 bps (default 9600), Modbus ID 1-247, parity none, even or odd. Relays 1 and 2 can be assigned to voltage, current unbalance, energy limit or the digital input; for example relay 1 operates when voltage rises above 250 V. Event logs cover voltage rise and fall, power cut, and current, PF, THDV and THDI limits, with a THD limit of 8%. Accuracy is +/-0.2% for voltage and current, +/-0.5% for active power and +/-1% for reactive power.

Key points

  1. Voltage and current harmonic measurement up to the 41st; 3P4W connection; RS485 Modbus RTU.
  2. The TPM-05A measures neutral current via a neutral CT and shows real neutral current, vector sum and scalar sum separately.
  3. Supply 85-240 VAC 50/60 Hz, <6 VA; two relay outputs (5 A/250 VAC) and one digital input.
  4. CT ratio example: multiplier 20 for 100/5 A, CTR=0020; CTR range 1-5000.
  5. VTR range 1.0-999.9; example 34,500/110 V = 313.6.
  6. Communication 1200-115200 bps (default 9600), Modbus ID 1-247, parity none/even/odd.
  7. Accuracy: voltage and current +/-0.2%, active power +/-0.5%, reactive power +/-1%; operation -20 to 55 C; weight <300 g.
  8. Event logs: voltage rise/fall, power cut, current, PF, THDV and THDI limits (THD limit 8%).

Using it in design

  • For critical power distribution, prefer the TPM-05A to monitor harmonics and neutral current; fit the neutral CT on the neutral conductor.
  • Choose the CT above maximum load current with class 0.5, and enter the CT ratio as CTR at commissioning.
  • If medium voltage is metered, enter the voltage transformer ratio in VTR.
  • Assign unique Modbus IDs to devices on the same line; set speed and parity to the network for BMS or DCIM integration.
  • Assign the relays to overvoltage or unbalance alarms and use them as warning or control outputs.

Who should read it

Engineers doing panel energy monitoring and commissioning, and BMS/DCIM integrators.

Document contents

  1. Connection schemes
  2. Current transformer selection and connection
  3. Warnings
  4. Device maintenance
  5. General
  6. First operation
  7. Screen presentation
  8. Menu and settings
  9. CT and VT ratio setting
  10. Communication settings
  11. Relay task assignment
  12. Dimensions
  13. Technical specifications

Publication details

Authors
Tense Electric Electronics
Publisher
Tense Electric Electronics
Year
Year not stated
Document number
DK-070-6
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer documentation inspected. No redistribution permission established. Metadata and original brief summaries only; local downloads are research evidence, not a redistribution package.

Citation

Tense Electric Electronics TPM-05 and TPM-05A: User Manual. Tense Electric Electronics. DK-070-6. https://tense.com.tr/wp-content/uploads/2021/02/DK-070-6-TPM-05-TPM-05A_ING.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.