General Recommendations for a Federal Data Center Energy Management Dashboard Display (FEMP, July 2014)

U.S. DOE Federal Energy Management Program / Lawrence Berkeley National Laboratory · Rod Mahdavi

LBNL guidance on what energy information a data centre dashboard should show to IT managers, facility managers and executives, built around three measurement levels.

On this page

Overview

This document is a guidance paper dated July 2014, prepared by Lawrence Berkeley National Laboratory (LBNL) for the US DOE Federal Energy Management Program (FEMP). Its subject is what a data centre energy management dashboard should show to IT managers, facility managers and executives. The document is freely available.

The guidance defines three measurement levels: minimum (Level 1), best practical (Level 2) and state-of-the-art (Level 3). The indicated PUE estimate accuracy is about +30% for Level 1, +15% for Level 2 and better than +5% for Level 3. The author recommends a Level 3 measurement package, subject to budget.

The document also provides example dashboards for PUE, end-use energy and capacity management; examples for all users, IT managers and facility managers using Level 3 tools appear in Figures 4-6. Its scope is a 2014 federal facility context, so dashboard layouts should be adapted to today's tools, but the relationship between measurement level and uncertainty remains a useful guide.

Key points

  1. Three measurement levels are defined: minimum (Level 1), best practical (Level 2), state-of-the-art (Level 3).
  2. Indicated PUE estimate accuracy: about +30% for Level 1, +15% for Level 2, better than +5% for Level 3.
  3. The author recommends a Level 3 measurement package, subject to budget.
  4. Example dashboards for all users, IT managers and facility managers using Level 3 tools (Figures 4-6).
  5. Examples cover PUE, end-use energy and capacity management.
  6. Audience is IT managers, facility managers and executives.
  7. Related reference: The Green Grid PUE measurement categories.

Using it in design

  • Compare Level 1, 2 and 3 metering coverage and state the resulting PUE uncertainty range in the metering plan.
  • Arrange energy dashboard reports around the information needed by each role.
  • Show the accuracy gain explicitly when metering budget decisions are made.

Who should read it

Engineers designing data centre energy metering and monitoring dashboards, and facility and IT managers.

Related standards

  • The Green Grid PUE measurement categories

Publication details

Authors
Rod Mahdavi
Publisher
U.S. DOE Federal Energy Management Program / Lawrence Berkeley National Laboratory
Year
2014
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Prepared for DOE FEMP by a national-laboratory contractor (stated on cover); not US-Gov public domain. Cited only.

Citation

Rod Mahdavi (2014). General Recommendations for a Federal Data Center Energy Management Dashboard Display (FEMP, July 2014). U.S. DOE Federal Energy Management Program / Lawrence Berkeley National Laboratory. https://www.energy.gov/cmei/femp/articles/general-recommendations-federal-data-center-energy-management-dashboard-display

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.