Research on the Fire Hazard of Different Cables Based on Cone Calorimetry
Fire / MDPI · Bobo Shi, Chenyang Yang et al.
A 2023 Fire (MDPI) study using ISO 5660 cone calorimetry on electrical cable, wire, optical fibre and network cable: fire risk rises with radiation intensity, and electrical cables pose the greatest overall fire hazard.
On this page
Overview
The study examines the combustion characteristics of frequently used cables, including electrical cables, wires, optical fibres and network cables, using ISO 5660 cone calorimetry. Time to ignition (TTI), heat release rate per unit area (HRRPUA), peak heat release rate (PHRR), total heat release (THR) and mass loss rate (MLR) are investigated for each cable type under different radiation intensities. Experiments show that the fire risk of all four cable types increases with external radiation intensity, with electrical cables posing the greatest risk.
For smoke toxicity, the lowest risk is the network cable with a fractional effective dose (FED) of 0.0203, followed by electrical wires at 0.0417, electrical cables at 0.0501 and optical fibres at 0.0507. No significant distinctions were seen among the other three, and the smoke toxicity of all four did not reach lethal concentration levels for humans. Considering thermal hazard and smoke toxicity together, electrical cables pose the greatest overall fire hazard. The authors state that chlorine gas measurements were unavailable and focus the toxicity analysis on measured smoke and carbon gases.
Key points
- Method: ISO 5660 cone calorimetry; measured TTI, HRRPUA, PHRR, THR and MLR.
- Samples: electrical cable, electrical wire, optical fibre and network cable under different radiation intensities.
- Fire risk of all four cable types rises with external radiation intensity; electrical cables pose the greatest risk.
- FED values: network cable 0.0203, electrical wire 0.0417, electrical cable 0.0501, optical fibre 0.0507.
- Smoke toxicity of all four did not reach lethal concentration for humans; chlorine gas could not be measured.
Using it in design
- Assess fire load in cable trays and cable-dense areas by cable type; electrical cables carried the greatest overall fire hazard in this study.
- Treat cable fire risk as higher where external radiation is elevated (hot aisle, near equipment).
- Separate network and optical cable density from power cable density in layouts to limit spread potential.
- In smoke toxicity assessment, note that the study did not include chlorine gas measurements.
Who should read it
Engineers designing data-centre cabling and fire load, and fire safety researchers.
Publication details
- Authors
- Bobo Shi; Chenyang Yang; Haifan Long
- Publisher
- Fire / MDPI
- Year
- 2023
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Article-specific CC BY 4.0 notice verified on the publisher page. Retain attribution, license link and change notices; third-party exceptions require separate review. Generic MDPI dc.rights metadata may say BY 3.0; the article-specific notice takes precedence. Round 5/6 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Bobo Shi; Chenyang Yang; Haifan Long (2023). Research on the Fire Hazard of Different Cables Based on Cone Calorimetry. Fire / MDPI. https://doi.org/10.3390/fire6110431
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
