A 98.8%-efficiency, thermally-optimized 48 V-to-12 V DC–DC converter for high-power data centers
Original title A 98.8%-efficiency, thermally-optimized 48 V-to-12 V DC–DC converter for high-power data centers
Frontiers in Electronics (Frontiers Media SA) · Ziqian Zhang
A brief research report on a 48 V-to-12 V converter built on a resonant switched-capacitor topology, with a circuit-board stack-up optimized for thermal and electrical efficiency.
On this page
Overview
The growth of AI and cloud workloads has raised the power demand of high-power processors (XPUs), and the transmission losses of conventional low-voltage delivery have become a problem. In that context, with 48 V delivery now the mainstream architecture, the paper concentrates on the 48 V-to-12 V intermediate-bus stage. Its introduction compares alternative topologies such as coupled inductors, buck-plus-switched-capacitor cascades and hybrid converters.
The proposed circuit is a cascaded resonant switched-capacitor (ReSC) converter operated with zero-current switching (ZCS). All MOSFETs run at the same frequency with a 50% duty cycle. The authors choose ReSC over LLC because it lowers switch voltage stress to about 36 V and needs no isolation transformer. The distinctive contribution is the comparison of two printed-circuit-board prototypes, one with six layers and one with eight.
In the experiments the converter reaches 96.1% full-load efficiency at 70 A and 98.8% peak efficiency. The eight-layer board is consistently more efficient than the six-layer one at the same current. Under fan cooling alone, the maximum temperature is 84.3 °C on the six-layer board and 73.7 °C on the eight-layer one. The DC resistance of the critical power path falls from about 0.45 mΩ to about 0.28 mΩ.
The report is a brief research article: one prototype, one power level and laboratory measurements. In the load-transient test, switching between 25% and 100% of rated load at 50 A/μs, the output voltage deviates by at most ±30 mV. For a data-centre designer, the value lies in the numerical demonstration of what determines efficiency and thermal design in the intermediate conversion stage of a 48 V architecture.
Key points
- With a resonant switched-capacitor topology and ZCS control, peak efficiency is 98.8% and full-load efficiency at 70 A is 96.1%.
- The ReSC structure lowers switch voltage stress to about 36 V instead of the full 48 V seen in an LLC, and uses smaller magnetics than an isolation transformer.
- Under fan cooling (8025 DC fan, 10 cm away, 3.6 m/s airflow) the maximum temperature is 84.3 °C on the six-layer board and 73.7 °C on the eight-layer board.
- The critical power-path DC resistance is about 0.45 mΩ in the six-layer design and about 0.28 mΩ in the eight-layer design; copper thickness goes from 2 oz to 4 oz and the current path shortens by about 15%.
- At 70 A, trace conduction loss alone falls by about 0.83 W; the rest of the roughly 1.5% total efficiency gain comes from lower semiconductor junction temperature.
- In the load-transient test the load swings between 25% and 100% of rated current at 50 A/μs; output voltage deviates by at most ±30 mV and recovers to within ±1% of nominal in 10 μs.
- Among designs reviewed in the introduction, a dual-bus converter reaches only 85.05% full-load efficiency, while a two-stage resonant prototype reaches 98.94% peak efficiency.
- Future work covers planar magnetics, GaN devices and intelligent control algorithms.
Using it in design
- In a 48 V intermediate-bus architecture, compare converter efficiency at full load rather than at peak only; here the difference is 98.8% versus 96.1%.
- In power-board selection, put copper thickness and layer count into the specification as efficiency and temperature criteria; board-related loss is measurable even at 70 A.
- In in-rack thermal design, evaluate the converter board surface temperature (73.7 to 84.3 °C in the example) together with airflow velocity and fan position.
- Compare load-transient requirements (25% to 100% swing, 50 A/μs) with the fast load changes of AI workloads and verify output voltage tolerance.
- In topology choice, tie the switch-voltage-stress and magnetics-size difference between ReSC and LLC to the power-density criterion.
Who should read it
Power-electronics engineers designing in-rack and intermediate-bus power conversion, and data-centre designers evaluating 48 V distribution architectures.
Document contents
- Abstract
- Introduction
- Circuit design and analysis
- Numerical calculation and simulation analysis
- Experimental results
- Conclusion
Related standards
- OCP Open Rack V3 (48 V)
Publication details
- Authors
- Ziqian Zhang
- Publisher
- Frontiers in Electronics (Frontiers Media SA)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- api.crossref.org
Original licence note
Creative Commons Attribution 4.0 International; licence verified from the Crossref licence metadata. Attribution to the authors and publisher is kept.
Citation
Ziqian Zhang (2026). A 98.8%-efficiency, thermally-optimized 48 V-to-12 V DC–DC converter for high-power data centers. Frontiers in Electronics (Frontiers Media SA). https://doi.org/10.3389/felec.2026.1697781
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.