Giganet GN-IR-3PH-6012A is a 380 V 3-phase 12 kW class direct-expansion in-row cooling unit giving 11.5 kW total capacity at 35 °C/26% RH return air and 12.2 kW at 37 °C/24% RH.

On this page

Overview

The datasheet presents Giganet's 12 kW in-row cooling unit, part number GN-IR-3PH-6012A. It is a fully closed inner-loop, row-based cooling unit that can be used without a dedicated data-centre room. Listed features include a built-in rack monitoring unit, optional integration with UPS, distribution and wiring, a double-layer tempered glass door, a dustproof low-noise design and easy relocation. Physical data are 300/600 mm width, 1000-1200 mm depth and 2000 mm height.

The EVO control system shows running status and the temperature and humidity of inlet and outlet air on a graphic display and supports teamwork of up to 32 units; RS485 is standard, with SNMP, TCP/IP and GPRS with SMS optional. An electronic expansion valve, DC inverter compressor and EC fan let capacity match heat load closely. The maker states energy saving of 20% for the DC inverter against an AC inverter and 50% against a constant-speed compressor, and 30% for the EC fan against an AC fan; starting current is low.

The technical table has two return-air conditions: 35 °C/26% RH and 37 °C/24% RH. Sensible heat ratio is 100%, so total and sensible capacity are equal. Maximum power is 8.0 kW, full load current 16.5 A, one compressor (rated power 2.7 and 2.9 kW), 6 EC fans (0.35 kW, total 2500 m3/h), heating 3 kW and humidification 3.0 kg/h. Dimensions: 600 mm wide, 1200 mm deep, 2000 mm high. The outdoor unit GN-IR-C16 has 10.5 A full load current, 1280 x 360 x 1260 mm, 125 kg, a 20 A breaker and 2.5 mm2 cable; the -40 to 45 °C range is achieved with a low-temperature startup kit.

Key points

  1. Total and sensible capacity 11.5 kW (35 °C/26% RH) and 12.2 kW (37 °C/24% RH); sensible heat ratio 100%.
  2. 380 V 3-phase 50 Hz; maximum power 8.0 kW, full load current 16.5 A.
  3. One compressor, rated power 2.7 and 2.9 kW; 6 EC fans, 0.35 kW, 2500 m3/h.
  4. Heating 3 kW; humidification 3.0 kg/h.
  5. Gas line 28 and 19 mm, liquid line 16 and 12.7 mm; drain inside diameter 25 mm.
  6. Outdoor unit GN-IR-C16: 1280 x 360 x 1260 mm, 125 kg, full load current 10.5 A, 20 A breaker, 2.5 mm2 cable.
  7. DC inverter compressor, EC fans and electronic expansion valve; networking of up to 32 units.

Using it in design

  • Use capacity with the return-air condition (35 °C/26% RH or 37 °C/24% RH); request curves from the maker if the room temperature differs.
  • Use maximum power and full load current for UPS and panel sizing, and the outdoor-unit current as a separate feeder.
  • Use gas and liquid line sizes in the indoor-to-outdoor pipe route and length check.
  • Plan to manage in-row units in a contained-aisle layout on one network of up to 32 units and to connect to the BMS over RS485 or SNMP.
  • Compare the outdoor unit's operating temperature range (including the low-temperature kit) with the site climate.

Who should read it

Mechanical designers selecting direct-expansion in-row cooling and planners of small and medium data halls.

Document contents

  1. Features
  2. Features of the Giganet in-row cooling unit (EVO control, electronic expansion valve, reliability, energy saving)
  3. Performance technical data
  4. Indoor EC fan data
  5. Heating and humidification
  6. Connection size and dimensions
  7. Outdoor unit technical data

Publication details

Authors
Giganet
Publisher
Giganet
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Giganet Giganet GN-IR-3PH-6012A datasheet, p.2. Giganet. https://www.giga-net.co.uk/_files/ugd/331712_b84fbc83dfcc45c0913dd5749d724bfa.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.