Grundfos Data Center Solutions - Keep your cool: Efficient water solutions for effective data flow

Grundfos

Grundfos's June 2023 data-centre brochure presents its cooling and water-distribution pump range (KPVS, NBSE, TPE3, CR, Hydro MPC) with up to IE5 efficiency and up to 2N+1 redundancy.

On this page

Overview

This June 2023 Grundfos brochure summarises water solutions for new, retrofit or modular data centres from Tier 1 to Tier 4. There are two headings: cooling, and water treatment and distribution. On cooling it lists smart pumps up to IE5 efficiency, up to 2N+1 redundancy, high-density liquid cooling and easy commissioning. On water it covers distribution, treatment against legionella, wastewater solutions and BMS/SCADA integration.

The cooling section describes pumps product by product. KPVS split-case vertical pumps reach up to 13,000 gpm (2,953 m³/h) and 420 ft (128 m) head. NBSE end-suction pumps reach 1,200 gpm and 270 ft, TPE3 inline pumps 500 gpm and 80 ft, and CR vertical multistage pumps 1,060 gpm and 1,000 ft. Hydro MPC is a pre-packaged system of two to six pumps with up to 6,000 gpm.

Efficiency claims rest on permanent magnet motors: up to 10% lower energy cost than NEMA Premium and up to 35% when integrated with a VFD. Distributed Pumping replaces conventional control valves with intelligent pumps and claims up to 80% savings in annual pumping power and a significantly higher delta T. These are manufacturer claims and the brochure gives no measurement conditions.

The brochure is marketing material and has no calculation method. The product ranges and liquid temperature limits are useful as first-pass screening data for pump selection.

Key points

  1. Pumps up to IE5 efficiency; up to 2N+1 redundancy; Tier 1-4 applications.
  2. KPVS: up to 13,000 gpm (2,953 m³/h), 420 ft (128 m), liquid temperature -20 °F to 275 °F.
  3. NBSE: up to 1,200 gpm and 270 ft; 35% smaller footprint than base-mounted pumps.
  4. TPE3 and TPE3D: up to 500 gpm and 80 ft; up to four pumps connect wirelessly in cascade mode.
  5. CR: up to 1,060 gpm and 1,000 ft; Hydro MPC: 2-6 pumps, up to 6,000 gpm.
  6. Permanent magnet motor: up to 10% lower energy cost than NEMA Premium, up to 35% with a VFD.
  7. Distributed Pumping: up to 80% savings in annual pumping power and a significantly higher delta T claimed.
  8. Water treatment covers legionella control, wastewater solutions and BMS/SCADA integration.

Using it in design

  • For the chilled-water circuit, set the redundancy pattern (N+1, 2N, 2N+1) from the facility target; the TPE3D dual-head pump gives built-in redundancy.
  • Model the Distributed Pumping claim (up to 80% annual pumping power savings) with your own load profile; the brochure gives no conditions.
  • Assess pump efficiency by motor class (IE5) and VFD together, against DOE pump energy index (PEI) requirements.
  • For CDU and chip-cooling loops, check fluid compatibility (dielectric fluid, glycol) and temperature range on the pump side.
  • Integrate pump data and sensors with the BMS and SCADA for predictive maintenance.

Who should read it

Mechanical designers selecting pumps for data-centre chilled-water and water distribution systems.

Document contents

  1. Efficiency and redundancy goals
  2. Cooling
  3. Water treatment and distribution
  4. Data centre cooling solutions and pump products
  5. Engineered systems
  6. Sustainability

Publication details

Authors
Grundfos
Publisher
Grundfos
Year
2023
Document number
LCBSSL07
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

© Grundfos Holding A/S LCBSSL07 06.2023

Citation

Grundfos (2023). Grundfos Data Center Solutions - Keep your cool: Efficient water solutions for effective data flow. Grundfos. LCBSSL07. https://api.grundfos.com/literature/Grundfosliterature-6859960.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.