Topic

Water

Find references on data centre water consumption, cooling water and water efficiency. Investigate local conditions, measurement boundaries and the relationship between energy and water use through technical notes.

Key numbers

Values hold under the conditions stated in each source. Read the cited page before using one in your project.

QuantityValueConditionSource
Upper WUE reported for evaporative systems2.5 L/kWhDry facilities with closed-loop liquid cooling need essentially no waterFluids (MDPI AG), 2026 · p. 1
Annual water use of a 1 MW data centre25.5 million litresTraditional evaporative or cooling-tower coolingnpj Clean Water (Springer Science and Business Media LLC), 2021 · p. 3
Maximum water conductivity1,500 uS/cmAt 25 C after treatment; dissolved copper below 0.2 ppmOpen Compute Project Foundation, 2023 · p. 8
Lower outlet temperature with evaporative than dry cooling16 KAt minimum outlet temperature, up to this muchEnergies (MDPI AG), 2023 · p. 1

Design checklist

  1. Meter every water source entering the boundary, with potable water separate. (European Commission (Official Journal of the European Union), 2024)
  2. Write the water-based fluid targets (TSS, TDS, conductivity, copper and iron, pH, hardness, turbidity, bacteria, azole inhibitor, chloride) into the fluid specification as acceptance criteria. (Open Compute Project Foundation, 2023)
  3. Compute and report WUE (L/kWh IT) next to PUE for every cooling design. (Schneider Electric, 2026)
  4. In water-footprint planning, calculate on-site (WUE), off-site electricity (PUE × EWIF) and embodied hardware water as separate items. (Journal of Cleaner Production (Elsevier BV), 2025)
  5. Keep evaporation, drift, leaks and blowdown as separate items in the cooling tower water balance. (U.S. Department of Energy / FEMP)

Start with these sources

Is Power Usage Effectiveness (PUE) Still Fit for Purpose? An Integrative Review of Data Center Metrics for Assessing the Environmental Impact of Modern AI Infrastructure

Journal of Science Policy & Governance (Journal of Science Policy and Governance, Inc.), 2026, Research paper

A policy-oriented integrative review asking whether PUE still works for high-density AI facilities, identifying four blind spots and proposing a four-axis dashboard instead of a single metric.

Research paper

2026

Read at publisher (opens in a new tab)

Related standards and regulations

Calculators and product

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

All documents in this topic

1–24 / 209

Is Power Usage Effectiveness (PUE) Still Fit for Purpose? An Integrative Review of Data Center Metrics for Assessing the Environmental Impact of Modern AI Infrastructure

Journal of Science Policy & Governance (Journal of Science Policy and Governance, Inc.), 2026, Research paper

A policy-oriented integrative review asking whether PUE still works for high-density AI facilities, identifying four blind spots and proposing a four-axis dashboard instead of a single metric.

Research paper

2026

Read at publisher (opens in a new tab)