Best Management Practice #10: Cooling Tower Management
U.S. Department of Energy / FEMP · U.S. Department of Energy Federal Energy Management Program (FEMP)
This US Department of Energy FEMP guide explains cooling-tower water losses, make-up water and concentration control, and ties blowdown management to water conservation.
On this page
Overview
The guide builds the tower water balance from three items: make-up replaces evaporation, blowdown and drift losses. Basin leaks or overflow add losses that must also be addressed. Measuring make-up alone therefore does not show how much of the water does useful work. A rise on the make-up meter therefore cannot be interpreted until it is split into evaporation, blowdown and leakage.
Cycles of concentration compare dissolved solids in blowdown and make-up water, and can be approximated by the make-up-to-blowdown volume ratio when other losses are negligible. If drift is neglected, make-up equals evaporation plus blowdown, so blowdown = evaporation / (cycles - 1); at 4 cycles, for example, blowdown is one third of evaporation. This derivation is a simple consequence of the relations, not the document's own statement.
The permissible concentration depends on source-water quality and treatment, so the guide does not impose one number. A tower balance is not whole-site WUE: water used in power generation and other uses sits outside it. Water savings are therefore sought in two steps: first the loss items (leaks, overflow) are closed, then the concentration cycle is raised up to the limit the treatment programme allows, which reduces blowdown.
Key points
- Tower make-up replaces evaporation, blowdown and drift losses.
- Basin leaks or overflow add losses that must also be addressed.
- Cycles of concentration compare dissolved solids in blowdown and make-up water.
- With other losses negligible, cycles can be approximated by the make-up-to-blowdown volume ratio.
- Permissible concentration depends on source-water quality and treatment.
Using it in design
- Keep evaporation, drift, leaks and blowdown as separate items in the model.
- Set the concentration limit with a water-treatment justification; do not hard-code a default.
- Do not present the tower balance as whole-site WUE.
Who should read it
Mechanical designers and plant operators computing cooling-tower water balance and consumption.
Publication details
- Authors
- U.S. Department of Energy Federal Energy Management Program (FEMP)
- Publisher
- U.S. Department of Energy / FEMP
- Year
- Year not stated
- Document number
- FEMP BMP 10
- Document language
- English
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
U.S. Department of Energy Federal Energy Management Program (FEMP) Best Management Practice #10: Cooling Tower Management. U.S. Department of Energy / FEMP. FEMP BMP 10. https://www.energy.gov/cmei/femp/best-management-practice-10-cooling-tower-management
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.