Cooling Water Efficiency Opportunities for Federal Data Centers
U.S. Department of Energy, Federal Energy Management Program
A US DOE FEMP page listing low-cost operating measures (setpoints, air management, economizers, COC) and technology options for tower-cooled data centres; raising COC from 3 to 6 cuts make-up 20% and blowdown 50%.
On this page
Overview
The US Federal Energy Management Program (FEMP) offers water efficiency strategies for cooling systems with cooling towers in new and existing federal data centres and resources to identify water-saving opportunities. The page gives a schematic of a typical data centre relying on tower evaporation and defines two metrics: PUE (total annual facility energy over IT energy; average efficient data centres 2.0, highly efficient ones approaching 1.0) and WUE (annual site water use in litres over IT energy in kWh, L/kWh).
Low-cost O&M measures are: room temperatures are often controlled well below recommended setpoints and humidity within an over-narrow range, raising chiller demand and tower water use; air management that separates hot and cool zones; air-side economizing in cool nights and mild seasons, since data centres run a steady 24-hour load; and water-side economizing that bypasses the chiller and removes compressor heat (up to 20% of total heat rejection). A heat exchanger in series upstream of the chillers gives first-stage cooling, saving water and energy.
COC is described as the ratio of make-up to blowdown volume; systems commonly run at two to four cycles and six or more may be possible. Per FEMP's Cooling Tower Best Management Practice, raising cycles from three to six reduces make-up water by 20% and blowdown by 50%. Technology options: thermal storage (water and energy savings may not be significant and it reduces air-side economizing potential), side stream filtration (keeps the tower near design efficiency but does not by itself cut energy or water use), reverse osmosis on blowdown (permeate reused as make-up, but high energy demand hurts PUE) and direct liquid cooling.
Direct liquid cooling transfers heat directly to a chilled water loop rather than to room air; pumping is typically more efficient than fans and water carries far more heat than air. Applications at Sandia National Laboratories and NLR show the Thermosyphon Cooler Hybrid System, which combines direct liquid cooling with air-cooled heat rejection and an open tower; it uses the tower during hot daytime hours and switches to air-cooled rejection when ambient is cool.
Key points
- PUE = total annual facility energy / IT annual energy; 2.0 for average efficient data centres, approaching 1.0 for highly efficient ones.
- WUE = annual site water use (litres) / IT annual energy (kWh).
- Room temperature and humidity are often controlled tighter than needed, raising chiller demand and tower water.
- Water-side economizing removes compressor heat, which can be up to 20% of total heat rejection.
- Systems commonly run at two to four cycles; six or more is possible.
- Raising cycles from 3 to 6 cuts make-up water by 20% and blowdown by 50%.
- Thermal storage may not give significant water or energy savings and reduces air-side economizing potential.
- Side stream filtration keeps the tower near design efficiency but does not alone cut water or energy use.
- Reverse osmosis on blowdown reuses permeate as make-up but its high energy demand hurts PUE.
Using it in design
- Widen room setpoint and humidity bands within equipment requirements to cut chiller load and tower water.
- Use air management separating hot and cool zones to limit mixing.
- Assess air-side and water-side economizing (heat exchanger in series with chillers) at design stage.
- Design tower treatment for COC of 6 or more and verify with blowdown and make-up meters.
- If adding reverse osmosis or side stream filtration, weigh the PUE effect and added O&M cost together.
Who should read it
Engineers and energy managers planning operating and water efficiency improvements in federal and other tower-cooled data centres.
Document contents
- Typical Data Center Cooling System
- Low-Cost/No-Cost Water-Saving Opportunities at Existing Data Centers
- Space Temperature and Humidity Control
- Air Management
- Use of Air-Side Economizing Strategies
- Use of Water-Side Economizing Strategies
- Maximizing Cycles of Concentration
- Technology Options
- Thermal Storage Technologies
- Side Stream Filtration
- Reverse Osmosis Treatment Systems
- Direct Liquid Cooling Systems
Publication details
- Authors
- U.S. Department of Energy, Federal Energy Management Program
- Publisher
- U.S. Department of Energy, Federal Energy Management Program
- Year
- Year not stated
- Document language
- English
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public publisher source inspected. No document-specific commercial redistribution permission established; metadata and original short summaries only. Local downloads are research evidence, not a redistribution package.
Citation
U.S. Department of Energy, Federal Energy Management Program Cooling Water Efficiency Opportunities for Federal Data Centers. U.S. Department of Energy, Federal Energy Management Program. https://www.energy.gov/cmei/femp/cooling-water-efficiency-opportunities-federal-data-centers
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
