Technical guideFree to read2025

A Guide to Data Center Cooling

Belimo

Belimo's 2025 guide explains position, flow, thermal-power and differential-pressure control in liquid-cooled racks and links changes in connected cold plates to the need for stable hydraulic control.

On this page

Overview

The guide, published on Belimo's blog, describes valve- and sensor-based control types for data-centre cooling: position control, flow control, thermal-power control and differential-pressure control. The focus is liquid-cooled racks.

Thermal-power control combines flow measurement with the supply/return temperature difference. The guide also covers rack pressure control when servers with cold plates are removed or swapped, and shows that changes in the number of connected cold plates require stable hydraulic control and monitoring.

Key points

  1. Position, flow, thermal-power and differential-pressure control are explained.
  2. Thermal-power control combines flow measurement with supply/return temperature difference.
  3. Rack pressure control is discussed for removal or swapping of cold-plate servers.
  4. Changes in the number of connected cold plates require stable hydraulic control and monitoring.

Using it in design

  • In liquid-cooled rack circuits, add pressure-independent flow or differential-pressure control to the design.
  • For thermal-power measurement, list the flow sensor and supply/return temperature sensors in the metering point list.
  • Define control logic that keeps rack pressure stable during server removal and swap scenarios.
  • Carry flow, temperature difference and pressure data to the BMS for monitoring.

Who should read it

Mechanical and controls engineers designing hydraulic control and monitoring for liquid-cooled data centres.

Publication details

Authors
Belimo
Publisher
Belimo
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public manufacturer document or page inspected. No document-specific redistribution permission established; retain metadata and original short summaries only.

Citation

Belimo (2025). A Guide to Data Center Cooling. Belimo. https://belimo.com/us/en_US/blog/a-guide-to-data-center-cooling

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.