Research paperPDF2026

A Review of Thermal Management in Modern Data Centres: Water Usage Effectiveness and Heat Transfer Coefficients

Fluids (MDPI AG) · Andre Cooper, Thi Bang Tuyen Nguyen

A review that builds a combined dataset of reported WUE for 83 data-centre entries, groups them by heat-rejection topology (dry, free-cooling, hybrid, evaporative), and uses one-dimensional heat-transfer models to compare the heat-transfer coefficients of air cooling, single-phase immersion, direct liquid cooling and two-phase immersion.

CC BY 4.0: share with attribution

On this page

Overview

Rapid growth in AI, machine learning and high-performance computing has substantially raised rack power densities, and because water remains widely used in cooling systems, understanding the relationship between cooling technologies and water consumption is essential. The review presents a survey of reported WUE across 83 data-centre entries as a combined dataset linking WUE with heat-rejection categories. It then uses one-dimensional heat-transfer models to compare heat-transfer coefficients of four mechanisms and converts them into an upper-bound equivalent evaporative water demand assuming all heat is rejected by direct evaporation (latent heat 2260 kJ/kg).

Of the 83 entries, 23 exceed 0.4 L/kWh, the Climate Neutral Data Centre Pact target for new facilities in water-stressed regions using potable water. Dry facilities with closed-loop liquid cooling need essentially no water, while evaporative systems typically report WUE up to 2.5 L/kWh. Two-phase immersion cooling can give heat-transfer coefficients about three orders of magnitude higher than air cooling. For direct liquid cooling at about 20 K excess temperature, equivalent evaporative water demand is about 0.4 L/kWh, an upper bound assuming all heat is rejected by direct evaporation.

The central argument is that reported WUE is a facility-level operational metric set by the proportion of the IT heat load rejected by evaporation, which depends on heat-rejection topology, ambient wet-bulb conditions and operating setpoints. High server-side heat-transfer coefficients enable dry rejection rather than determine WUE directly. WUE is an annual-average relative metric that hides seasonal peaks, and a large site with low WUE can still use more total water than a small site with high WUE.

Limits: the WUE dataset comes mainly from corporate disclosures, is not independently verified, may suffer selection bias and is weighted toward Europe, North America and Australia. The heat-transfer analysis rests on an order-of-magnitude one-dimensional model.

Key points

  1. Of 83 reported data-centre WUE entries, 23 exceed 0.4 L/kWh, the Climate Neutral Data Centre Pact target for new facilities in water-stressed regions using potable water.
  2. Dry facilities with closed-loop liquid cooling need essentially no water, while evaporative systems typically report WUE up to 2.5 L/kWh.
  3. Two-phase immersion cooling can give heat-transfer coefficients about three orders of magnitude higher than air cooling.
  4. For direct liquid cooling at about 20 K excess temperature, equivalent evaporative water demand is about 0.4 L/kWh, an upper bound assuming all heat is rejected by direct evaporation (latent heat 2260 kJ/kg).
  5. WUE is an annual-average relative metric; it hides seasonal peaks, and a large site with low WUE can still use more total water than a small site with high WUE.
  6. The WUE dataset comes mainly from corporate disclosures, is not independently verified, may suffer selection bias and is weighted toward Europe, North America and Australia.

Using it in design

  • Set WUE targets from the heat-rejection topology (dry, free-cooling, hybrid, evaporative) and not only the server-side cooling technology; WUE depends on the share of heat rejected by evaporation.
  • Report the 0.4 L/kWh threshold (CNDCP) together with total water volume; WUE is an annual average and hides seasonal peaks and total consumption.
  • In high-density racks use liquid cooling's high heat-transfer coefficient to enable dry heat rejection, and back WUE claims with independently verified data.

Who should read it

Cooling designers and sustainability managers setting data-centre water targets and heat-rejection topology.

Document contents

  1. 1. Introduction
  2. 2. Methodology (2.1 Literature Review Methodology, 2.2 Modelling: general modelling framework, convective cooling, two-phase immersion cooling)
  3. 3. Results (3.1 Review Summary: general insights into data centre cooling, thermal management pathway; 3.2 Water Usage Effectiveness (WUE); 3.3 Categorising Heat-Rejection Topology; 3.4 Modelling Results: heat transfer coefficients, heat dissipation flux and equivalent evaporative water demand)
  4. 4. Conclusions

Related standards

  • ISO/IEC 30134-9 (WUE)
  • Climate Neutral Data Centre Pact
  • The Green Grid WP35 (WUE)

Read the document

dc-thermal-management-wue-review-2026.pdf

PDF · 2.8 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Andre Cooper; Thi Bang Tuyen Nguyen
Publisher
Fluids (MDPI AG)
Year
2026
Volume
11
Issue
8
Pages
201
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
www.mdpi.com
Original licence note

p.1 states the article is open access under the Creative Commons Attribution (CC BY) licence.

Citation

Andre Cooper; Thi Bang Tuyen Nguyen (2026). A Review of Thermal Management in Modern Data Centres: Water Usage Effectiveness and Heat Transfer Coefficients. Fluids (MDPI AG). 11(8), 201. https://doi.org/10.3390/fluids11080201

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.