Technical guideFree to read2024

Fluid Dynamics: Liquid Cooling's Role in the Future of Data Centers

Burns & McDonnell · Sam Allen

A five-page Burns & McDonnell white paper describing three liquid cooling approaches at the IT level (rear-door heat exchangers, direct-to-chip and immersion) and their effect on facility design.

On this page

Overview

This five-page 2024 Burns & McDonnell white paper by Sam Allen describes three liquid cooling approaches at the IT level: rear-door heat exchangers (RDHX), direct-to-chip and immersion. It explains the split between the technology cooling system (TCS) and the facility water system via CDUs, and why facility water is not piped straight to IT equipment.

On density, liquid-cooled halls are being built at about 10x the density of air-cooled ones; some solutions reach 80-120+ kW per rack versus a typical 8-12 kW. Liquid gives roughly 3,200x more heat capacity per unit volume than air. An RDHX transfers about 100% of server heat to the TCS and discharges air at about cold-aisle temperature, so containment matters less.

Even with 100% liquid-cooled IT, about 20-50% of the IT load still needs air cooling (convection losses plus air-cooled network racks). Facility water is kept off the IT because of purity requirements and to limit the water volume per circuit if a leak occurs. If dry coolers can reject heat in all hours for the climate, WUE tends to zero.

In energy accounting, CDU pumps take over server fan energy, moving consumption from the PUE denominator to the numerator, and TUE is suggested as a fairer comparison. The paper also touches on fluid choice, the change in staff skills and the reuse of higher-grade waste heat. As a limitation, it is a five-page overview and offers no calculation method.

Key points

  1. Liquid-cooled halls are being built at about 10x the density of air-cooled ones.
  2. Some solutions reach 80-120+ kW per rack versus a typical 8-12 kW.
  3. Liquid gives roughly 3,200x more heat capacity per unit volume than air.
  4. An RDHX transfers about 100% of server heat to the TCS and discharges air at about cold-aisle temperature.
  5. Even with 100% liquid-cooled IT, about 20-50% of the IT load still needs air cooling.
  6. Facility water is kept off the IT because of purity requirements and to limit water volume per circuit on a leak.
  7. CDU pumps take over server fan energy, moving consumption from the PUE denominator to the numerator; TUE is suggested.
  8. If dry coolers can reject heat in all hours for the climate, WUE tends to zero.

Using it in design

  • Calculate the residual air-cooling load for liquid-cooled racks. Verify the source’s 20–50% of IT assumption for the project and size CRAH or fan-wall capacity accordingly.
  • Treat the CDU as the boundary between TCS and facility water, recording fluid type and loop volume.
  • Show a warning when PUE comparisons between air and liquid designs ignore server fan power.

Who should read it

Data centre mechanical designers and decision makers planning a move to liquid cooling.

Related standards

  • ASHRAE TC 9.9 Liquid Cooling Guidelines

Publication details

Authors
Sam Allen
Publisher
Burns & McDonnell
Year
2024
Document number
673770
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Sam Allen (2024). Fluid Dynamics: Liquid Cooling's Role in the Future of Data Centers. Burns & McDonnell. 673770. https://info.burnsmcd.com/hubfs/Collateral/White%20Papers/GFS_KCM_LiquidCoolingforDataCenters_673770_WP/Fluid-Dynamics-Liquid-Coolings-Role-in-Future-of-Data-Centers-white-paper-burns-mcdonnell-673770.pdf?hsLang=en

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.