Research paperPDF2021

Data centre water consumption

npj Clean Water (Springer Science and Business Media LLC) · David Mytton

A perspective that reviews how data centres consume water: directly through evaporative and cooling-tower heat rejection and indirectly through electricity generation, and how the sector measures and reports this use.

CC BY 4.0: share with attribution

On this page

Overview

The ICT sector will grow, with 29.3 billion devices expected online by 2030, up from 18.4 billion in 2018. Data-centre energy consumption regularly receives coverage, but analysis of water consumption is scarce. The paper examines how data centres consume water directly for cooling, in some cases 57% sourced from potable water, and indirectly through the water requirements of non-renewable electricity generation. In the USA, data-centre water consumption is about 1.7 billion litres/day, against total US consumption of 1218 billion litres/day.

Context figures: the US average water intensity of electricity generation in 2015 was 2.18 L/kWh; consumption for hydropower is 16.8 L/kWh, compared with 1.25 L/kWh for thermoelectricity. Digital Realty sourced 64% (2017), 65% (2018) and 57% (2019) of its water from potable supplies. A small 1 MW data centre using traditional evaporative or cooling-tower cooling can use around 25.5 million litres of water per year. Raising chilled-water temperature from the usual 7-10 °C to 18-20 °C can cut expenses by 40%.

WUEsource adds annual source-energy water use to annual site water use and divides by ICT equipment energy; the author recommends that cloud vendors calculate and publish it alongside PUE. Less than a third of data-centre operators track any water metrics, and water conservation is ranked as a low priority. Electricity generation is the largest contributor to a data centre's water footprint but is invisible without metrics like WUEsource. Moving to the cloud is more efficient, but transparency is a major issue: Microsoft and Google produce detailed but aggregate environmental reports, and Amazon publishes almost nothing.

Limits: a perspective with no new measurements; values are collected from published company reports and generic grid water intensities. Industry directions listed include free cooling, higher chilled-water temperatures, recycled water, liquid cooling and siting.

Key points

  1. US data-centre water consumption is about 1.7 billion litres/day, compared with total US consumption of 1218 billion litres/day.
  2. The US average water intensity of electricity generation in 2015 was 2.18 L/kWh; consumption for hydropower is 16.8 L/kWh, compared with 1.25 L/kWh for thermoelectricity.
  3. Digital Realty sourced 64% (2017), 65% (2018) and 57% (2019) of its water from potable supplies.
  4. A small 1 MW data centre using traditional evaporative or cooling-tower cooling can use around 25.5 million litres of water per year.
  5. Raising chilled-water temperature from the usual 7-10 °C to 18-20 °C can cut expenses by 40%.
  6. Less than a third of data-centre operators track any water metrics, and water conservation is ranked as a low priority.
  7. WUEsource adds annual source-energy water use to annual site water use and divides by ICT equipment energy; the author recommends cloud vendors publish it alongside PUE.

Using it in design

  • In cooling selection, add the roughly 25.5 million litres per year per MW of evaporative cooling water need and the potable share (57-65%) to the siting and water supply decision.
  • Evaluate raising chilled-water temperature from 7-10 °C to 18-20 °C and free cooling as both energy and water reduction options (expenses can fall 40%).
  • Report WUE and WUEsource (including indirect water from electricity) alongside PUE.

Who should read it

Designers and sustainability managers evaluating data-centre water use, reporting and cooling selection.

Document contents

  1. Introduction
  2. Direct and indirect water use in data centres
  3. Measuring and reporting water consumption: WUE and WUEsource
  4. Published hyperscaler figures and grid water intensities
  5. Industry directions: free cooling, higher chilled-water temperatures, recycled water, liquid cooling and siting
  6. Conclusions

Related standards

  • The Green Grid WP35 (WUE)
  • ISO/IEC 30134-9

Read the document

mytton-data-centre-water-consumption-2021.pdf

PDF · 0.6 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
David Mytton
Publisher
npj Clean Water (Springer Science and Business Media LLC)
Year
2021
Volume
4
Issue
1
Pages
11
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
www.nature.com
Original licence note

The article is marked OPEN and published under a Creative Commons Attribution 4.0 International License (see the licence statement at the end of the article).

Citation

David Mytton (2021). Data centre water consumption. npj Clean Water (Springer Science and Business Media LLC). 4(1), 11. https://doi.org/10.1038/s41545-021-00101-w

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.