Climate Neutral Data Centre Pact - Water Usage Metric Proposal (Summary and Annexes)

Climate Neutral Data Centre Pact (CNDCP) · Climate Neutral Data Centre Pact, Water Usage Working Group

The CNDCP's 2021 workshop proposal sets a location-dependent maximum WUE with WUEmax = K0 x K1 x K2 x K3; the target is 0.4 L/kWh for potable water, cool climate and high water stress.

On this page

Overview

The document records the outcome of the Climate Neutral Data Centre Pact water usage group workshops held from March to November 2021. The group concluded that responsible water use should be reflected in a single KPI that drives the most responsible cooling technology choice for a given location. The chosen metric is Water Usage Effectiveness, site value (WUE category 1) per ISO/IEC 30134-9, and the Pact establishes a location-dependent maximum.

The maximum WUE depends on three parameters: climate, water availability and water type. Operators cannot significantly influence the first two; the third is their responsibility. The formula is WUEmax = K0 x K1 (climate) x K2 (water stress) x K3 (water type), with K0 = 0.4 L/kWh. K1 is 1.0 for cooling degree days (CDD) < 50 and 1.1 for CDD ≥ 50. K2 is 5 for low water stress, 4 low-medium, 2.5 medium-high and 1 high (WEI+ bands 0-10, 10-20, 20-40, > 40). K3 is 1 for potable or fresh water, 3 for grey water and 6 for black, brackish or sea water.

Tabulated values: for potable water in a cold climate, low stress 2.00, low-medium 1.60, medium-high 1.00 and high 0.40 L/kWh; in a hot climate 2.20, 1.76, 1.10 and 0.44 L/kWh. Grey water values run from 1.20 to 6.60 L/kWh and black or salty water from 2.40 to 13.20 L/kWh. New data centres must meet the target by 2025; existing ones from 1 January 2025 when the cooling system reaches end of service life, and no later than 2040.

The annexes cover context, objectives (a simple, holistic model based on public physical data), the climate regionalisation approach (cold and hot, as in the Pact's PUE calibration), four water stress levels, water type, determination of correction factors and model analysis. Climate data for Europe are interpolated on 25 km grids.

Key points

  1. Metric: WUE site value (category 1) per ISO/IEC 30134-9; the Pact sets a location-dependent maximum.
  2. Formula: WUEmax = K0 x K1 x K2 x K3; K0 = 0.4 L/kWh.
  3. K1: 1.0 for CDD < 50 (cold), 1.1 for CDD ≥ 50 (hot).
  4. K2: water stress low 5, low-medium 4, medium-high 2.5, high 1 (WEI+ 0-10, 10-20, 20-40, > 40).
  5. K3: potable/fresh water 1, grey water 3, black/brackish/sea water 6.
  6. Potable water WUEmax ranges from 0.40 L/kWh (cold, high stress) to 2.20 L/kWh (hot, low stress).
  7. Grey water up to 6.60 L/kWh, black or salty water up to 13.20 L/kWh.
  8. New data centres meet the target by 2025; existing ones at end of cooling system life, no later than 2040.
  9. The climate split follows the Pact's PUE calibration approach; the operator can influence only the water type.

Using it in design

  • For a new European site, compute WUEmax from K0, K1, K2 and K3 and use it as a constraint when choosing the cooling architecture (evaporative or dry).
  • Determine site water stress with WEI+ (or a similar metric) and take CDD from European meteorological databases.
  • If grey water or other alternative sources are chosen, treat the WUE budget widened by K3 as a design opportunity.
  • Optimise the WUE and PUE trade-off together for the climate and location.
  • For existing sites, align the cooling system renewal schedule with the 2040 compliance date.

Who should read it

Engineers designing data centres in Europe and sustainability managers setting water targets under the CNDCP commitment.

Document contents

  1. Preamble and Synthesis
  2. Correction Factors and WUEmax Tables
  3. Context and Challenges
  4. Objectives of the Water Working Group
  5. Influencing Parameters: Climate, Water Availability, Water Type
  6. Modeling Principles
  7. Determination of Correction Factors
  8. Model Adjustment and Analysis

Related standards

  • ISO/IEC 30134-9:2022
  • ISO 14046
  • ISO 12056-1

Publication details

Authors
Climate Neutral Data Centre Pact, Water Usage Working Group
Publisher
Climate Neutral Data Centre Pact (CNDCP)
Year
2024
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No licence statement in the document or on the downloads page.

Citation

Climate Neutral Data Centre Pact, Water Usage Working Group (2024). Climate Neutral Data Centre Pact - Water Usage Metric Proposal (Summary and Annexes). Climate Neutral Data Centre Pact (CNDCP). https://www.climateneutraldatacentre.net/wp-content/uploads/2025/09/White-paper-on-DC-responsible-use-of-water-review-2024.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.