Finding Sustainable Solutions to Data Center Power and Water Use
Nortek Air Solutions · Philip LePoudre, Pooya Navid
This Nortek paper on the StatePoint Liquid Cooling system argues for designing cooling for typical annual conditions instead of 20- or 50-year extremes. A 20 MW Frankfurt colocation case compares pPUE and water use across plant types.
On this page
Overview
StatePoint is an indirect evaporative chilled-water plant built around a membrane exchanger that keeps air and water separate. The paper proposes designing for typical annual conditions and accepting brief, allowed excursions in supply-air temperature (SAT). In 100% free-cooling applications the plant reaches pPUE 1.05-1.06 (1.025-1.03 excluding fan-coil wall energy), with annualised WUE below 0.1 L/kWh depending on climate. The manufacturer claims annual water and power reductions of up to 90% and 60% versus chiller/cooling-tower plants; the early development target was 20-30%.
The Frankfurt case is a 20 MW colocation with 12 StatePoint units at N+2, compared with hybrid fluid coolers and open cooling towers on annual pPUE/WUE versus SAT. Raising annual SAT from 23 to 29 C markedly improves pPUE and WUE. The peak design condition pairs ASHRAE N50 dry bulb 39.1 C with N20 wet bulb 23.9 C; letting SAT rise into the ASHRAE A1/A2 allowable range at that extreme greatly reduces trim-chiller capacity.
The peak numbers give a separate result for electrical sizing. At 100% IT load, the ASHRAE 50-year extreme and 1-2 units offline, peak pPUE is 1.23 for StatePoint, 1.28 for the hybrid cooler and 1.275 for the cooling tower, which is about 230 kW versus 275-280 kW of cooling power per 1,000 kW of IT. Peak hourly make-up water is about 41% below the hybrid cooler and 6% below the cooling tower. The paper also covers the membrane's water-quality and Legionella advantages and smaller on-site water storage. The comparisons come from the manufacturer's own case study.
Key points
- In 100% free cooling, pPUE 1.05-1.06 (1.025-1.03 excluding fan-coil wall energy); annualised WUE <0.1 L/kWh depending on climate.
- Manufacturer claim: up to 90% less annual water and 60% less power than chiller/tower plants; early target 20-30%.
- Frankfurt: 20 MW colocation, 12 StatePoint units at N+2.
- Raising annual SAT from 23 to 29 C markedly improves pPUE and WUE.
- Peak condition: ASHRAE N50 dry bulb 39.1 C coincident with N20 wet bulb 23.9 C.
- Peak pPUE: StatePoint 1.23, hybrid cooler 1.28, cooling tower 1.275 (~230 kW versus 275-280 kW per 1,000 kW IT).
- Peak hourly make-up water ~41% below a hybrid cooler and ~6% below a cooling tower.
Using it in design
- Support peak pPUE (electrical sizing, with N-x units offline at ASHRAE N50/N20 extremes) separately from annual pPUE/WUE (energy) in the cooling plant model.
- Take allowable SAT excursion hours and ASHRAE A1/A2 limits as inputs; they drive trim-chiller sizing.
- Add an indirect evaporative chilled-water plant type to the catalog with a WUE curve versus SAT.
- Size make-up water and storage in the water assessment from peak instantaneous evaporation, not the annual average.
Who should read it
Design engineers and investment decision makers choosing cooling plant for water- and power-constrained sites.
Related standards
- ASHRAE TC 9.9 Thermal Guidelines
- ISO/IEC 30134-2
- ISO/IEC 30134-9
Publication details
- Authors
- Philip LePoudre; Pooya Navid
- Publisher
- Nortek Air Solutions
- Year
- 2021
- Document number
- 752F-0721
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Philip LePoudre; Pooya Navid (2021). Finding Sustainable Solutions to Data Center Power and Water Use. Nortek Air Solutions. 752F-0721. https://www.nortekdatacenter.com/wp-content/uploads/2021/07/752F-0721-NDCC-StatePoint-Solutions-to-Power-Water-Use-wp-1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.