How Chilled Water Systems Meet Data Center Availability and Sustainability Goals
Vertiv
This 2024 Vertiv paper assesses chilled-water cooling with TEWI and WUE and quantifies each efficiency step with a 15 MW simulation in three cities.
On this page
Overview
Cooling accounts for roughly 25-35% of data-centre energy in many facilities. The paper uses TEWI as its yardstick: direct refrigerant-leak emissions plus indirect electricity emissions. The formula is GWP x leakage rate x years, plus GWP x charge x (1 - recovery factor), plus years x annual energy x grid CO2 factor. For scroll chillers, R410A (GWP 1924) gives way to R454B (466), R32 (677) or R290; for screw and centrifugal chillers, R134a (1300) to R513A (573) or R1234ze (below 1).
Efficiency steps are shown in sequence: typical white space now runs at 24-25°C server inlet with 36-37°C return air, with chilled water raised from 10-15°C to 15-18°C or higher; then come free-cooling chillers, plant-level control, inverter compressors, adiabatic pads, heat recovery and thermal storage. The simulation basis is, per 5 MW hall, 5 (N+1) chillers of 1250 kW and 28 (N+1) CRAHs of 185 kW, at 80% load (12 MW total).
The results make each step concrete. Ashburn pPUE goes from a 10/15°C baseline of 1.217 to 1.128 with 20/28°C water and free-cooling chillers, 1.117 with plant control, 1.106 with inverter compressors and low-GWP refrigerant and 1.094 with adiabatic, while WUE rises from 0 to 0.277 L/kWh. In Tokyo the baseline of 1.235 falls to 1.108 with adiabatic (WUE 0.253 L/kWh). The paper also notes that 2-5 MW halls are moving to non-raised floors, where standard perimeter CRAHs can create high-velocity air and negative pressure at the first rack row.
Key points
- Cooling accounts for roughly 25-35% of data-centre energy in many facilities.
- TEWI = GWP x leakage rate x years + GWP x charge x (1 - recovery factor) + years x annual energy x grid CO2 factor.
- Refrigerant swaps: R410A (GWP 1924) to R454B (466), R32 (677) or R290 for scroll chillers; R134a (1300) to R513A (573) or R1234ze (<1) for screw/centrifugal.
- Typical white space now runs at 24-25°C server inlet with 36-37°C return air; chilled water is raised from 10-15°C to 15-18°C or higher.
- Simulation basis per 5 MW hall: 5 (N+1) chillers of 1250 kW and 28 (N+1) CRAHs of 185 kW at 80% load (12 MW total).
- Ashburn pPUE: baseline 10/15°C 1.217; 20/28°C water with free-cooling chillers 1.128; plant control 1.117; inverter compressor + low-GWP 1.106; adiabatic 1.094 (WUE 0 to 0.277 L/kWh).
- Tokyo equivalent: 1.235 baseline down to 1.108 with adiabatic (WUE 0.253 L/kWh).
- 2-5 MW halls are moving to non-raised floor; standard perimeter CRAHs can create high-velocity air and negative pressure at the first rack row.
Using it in design
- Add a TEWI calculation to cooling options (refrigerant GWP, charge kg, leak rate, life years, grid emission factor).
- For chiller selection, record refrigerant, GWP (AR5), free-cooling capability, adiabatic option and compressor type, and flag high-GWP refrigerants against F-gas and Kigali phase-down.
- Report pPUE and WUE together so adiabatic gains are never shown without their water cost.
- Warn on non-raised-floor halls with standard perimeter CRAHs near the first row.
Who should read it
Mechanical designers evaluating chilled-water plant architecture, refrigerant choice and adiabatic options.
Related standards
- ASHRAE TC 9.9 Thermal Guidelines
- EU F-gas Regulation
- ISO/IEC 30134-9 (WUE)
- ISO/IEC 30134-2 (PUE)
Publication details
- Authors
- Vertiv
- Publisher
- Vertiv
- Year
- 2024
- Document number
- SL-18066
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Vertiv (2024). How Chilled Water Systems Meet Data Center Availability and Sustainability Goals. Vertiv. SL-18066. https://www.vertiv.com/4a24eb/globalassets/shared/vertiv-chilled-water-solution-white-paper-sl-18066.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.