StandardFree to read2019

Water-Cooled Servers: Common Designs, Components, and Processes

ASHRAE TC 9.9

This 2019 ASHRAE TC 9.9 white paper (with errata) describes how water-cooled IT systems are built: the facility water system (FWS), the secondary technology cooling system (TCS) loop and the CDU between them. It gives separate water-quality limits for the two loops, the point most often confused.

On this page

Overview

The architecture has three layers: the facility water system (FWS), the secondary technology cooling system (TCS) loop, and the CDU separating them. Cold plates, wetted materials and controls are described too. The paper warns explicitly that the water-quality tables for the two loops are often mixed up. The condensation rule is clear: keep TCS supply at least 2 degC (3.6 degF) above the room dew point, using proportional, binary or bypass valves.

Filter size is dictated by the smallest flow path in the cold plate, and a 35-40 mesh (about 500-400 micron) strainer guideline is given for the FWS. Water-quality limits are split by loop. pH is 7-9 for FWS and 8.0-9.5 for TCS. Total hardness is below 200 ppm for FWS and below 20 ppm for TCS (as CaCO3). TCS conductivity is 0.2-20 micromho/cm, total suspended solids below 3 ppm and turbidity below 20 NTU.

The tenfold hardness gap shows why running both loops to one specification is an error. In the product survey, maximum facility-water temperatures ranged 10-24 degC for most products, and eight products accepted 40 degC or more. The paper also covers water treatment, monitoring and maintenance planning, but it is a white paper compiling common practice, not a design code. The tables show the TCS loop has to be kept far cleaner than the FWS loop.

Key points

  1. Keep TCS supply at least 2 degC (3.6 degF) above room dew point.
  2. pH: FWS 7-9; TCS 8.0-9.5.
  3. Total hardness: FWS under 200 ppm; TCS under 20 ppm (as CaCO3).
  4. TCS conductivity 0.2-20 micromho/cm; total suspended solids under 3 ppm; turbidity under 20 NTU.
  5. FWS strainer guideline 35-40 mesh (about 500-400 micron).
  6. Filter size is dictated by the smallest flow path in the cold plate.
  7. Surveyed products: max facility-water temperature 10-24 degC for most; 8 products at 40 degC or above.

Using it in design

  • Keep TCS supply temperature at least 2 °C above the room dew point.
  • Keep separate FWS and TCS water-quality specs (pH, hardness, conductivity, TSS) in commissioning checklists.
  • Default FWS strainer to 500 micron and TCS filter to 50 micron (with the Vertiv guide).
  • Identify facility-water and technology-cooling loops separately as FWS and TCS in the specifications.

Who should read it

Mechanical engineers who design, commission and operate water-cooled server loops.

Related standards

  • ASHRAE Liquid Cooling Guidelines for Datacom Equipment Centers
  • ASHRAE TC9.9 Thermal Guidelines (W classes)
  • OCP cold plate requirements

Publication details

Authors
ASHRAE TC 9.9
Publisher
ASHRAE TC 9.9
Year
2019
Document number
TC 9.9 White Paper
Document language
English
Source type
Standard
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

ASHRAE TC 9.9 (2019). Water-Cooled Servers: Common Designs, Components, and Processes. ASHRAE TC 9.9. TC 9.9 White Paper. https://www.ashrae.org/File%20Library/Technical%20Resources/Bookstore/Whitepaper_TC099-WaterCooledServers.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.