Single-Node Power Demand During AI Training: Measurements on an 8-GPU NVIDIA H100 System
IEEE Access (Institute of Electrical and Electronics Engineers (IEEE)) · Imran Latif, Alex C. Newkirk et al.
An IEEE Access 2025 paper measures a maximum of about 8.4 kW on an 8-GPU NVIDIA H100 HGX node, 18% below the manufacturer rating of 10.2 kW.
On this page
Overview
The paper measures the instantaneous power draw of an 8-GPU NVIDIA H100 HGX node while it trains ResNet image classifiers and the Llama2-13b large language model. The aim is to give the models needed to quantify the energy footprint of AI infrastructure a parameter for the power demand of AI hardware during training. The work characterises a single node configuration and provides foundational data for multi-node studies.
The main finding is that the maximum observed power draw was about 8.4 kW, 18% lower than the manufacturer-rated 10.2 kW, even with GPUs near full utilisation. Holding model architecture constant, increasing the ResNet batch size from 512 to 4096 images reduced total training energy consumption by a factor of 4. The results inform capacity planning by data centre operators and energy use estimates by researchers. Future work will examine the impact of cooling technology and carbon-aware scheduling.
Key points
- Instantaneous power was measured on an 8-GPU NVIDIA H100 HGX node training ResNet and Llama2-13b.
- Maximum observed node power was about 8.4 kW.
- This is 18% below the manufacturer rating of 10.2 kW even with GPUs near full utilisation.
- Increasing the ResNet batch size from 512 to 4096 cut total training energy by a factor of 4.
- The study covers a single node; multi-node and cooling effects are left to future work.
Using it in design
- For AI racks use the measured power curve rather than nameplate power as the capacity planning input, but set the safety margin by workload variety.
- Separate the 10.2 kW nameplate value as an upper bound for facility design load from the 8.4 kW measured value as typical heavy training load when sizing rack power distribution.
- In the energy budget reflect in operating scenarios that software settings such as batch size change total training energy.
- Do not multiply a single-node measurement directly to a multi-node cluster; assess network, cooling and coordination effects separately.
Who should read it
Data-centre operators and researchers planning power and energy capacity for AI training clusters.
Publication details
- Authors
- Imran Latif; Alex C. Newkirk; Matthew R. Carbone; Arslan Munir; Yuewei Lin; Jonathan Koomey; Xi Yu; Zhihua Dong
- Publisher
- IEEE Access (Institute of Electrical and Electronics Engineers (IEEE))
- Year
- 2025
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY-NC-ND 4.0: share unaltered with attribution for noncommercial purposes
Original licence note
Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by-nc-nd/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Non-commercial licence: link/cite only in a commercial product.
Citation
Imran Latif; Alex C. Newkirk; Matthew R. Carbone; Arslan Munir; Yuewei Lin; Jonathan Koomey; Xi Yu; Zhihua Dong (2025). Single-Node Power Demand During AI Training: Measurements on an 8-GPU NVIDIA H100 System. IEEE Access (Institute of Electrical and Electronics Engineers (IEEE)). https://doi.org/10.1109/access.2025.3554728
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.