VCA Series Large Server Room Chilled-water Precision Air Conditioner: Specifications

Original title INVT VCA Series Large Server Room Chilled-Water Precision Air Conditioner

INVT

INVT's VCA chilled-water precision air conditioners span 36.6 to 255.0 kW in 19 models, rated at 35 °C dry-bulb return air and 15/21 °C water, with all capacity sensible.

On this page

Overview

The page gives the product features and technical table of INVT Electric's VCA series chilled-water precision air conditioners for large server rooms. The series runs from VCA030 to VCA250 and supports upflow, top-front-with-plenum and downflow air supply modes.

Efficiency features include high airflow with low enthalpy difference, a backward-curved EC centrifugal fan with speed adjusted to heat load, a large A- or V-shaped cooling coil, a proportional two-way motorized water valve and an evaporative humidifier. In downflow configuration the unit is said to save more than 20% energy compared with conventional installations.

On reliability and control, the units offer intelligent power monitoring (phase loss, phase reversal, over- and undervoltage, over- and underfrequency), fault self-diagnosis, a 10-inch touchscreen, RS485 and SNMP interfaces, networking and group control of up to 64 units with scheduled and fault-based rotation, more than 2,000 stored records and automatic restart after power recovery. Dual power supply modules, surge protectors and a differential pressure sensor are optional.

The technical table shows total capacity equal to sensible capacity. Rating conditions are inlet air 35 °C dry-bulb and 21 °C wet-bulb, inlet water 15 °C and outlet water 21 °C. Power input is 380-415 V 3N~ 50/60 Hz.

Key points

  1. 19 models from VCA030 (36.6 kW) to VCA250 (255.0 kW); total capacity equals sensible capacity.
  2. Rating condition: air 35 °C dry-bulb / 21 °C wet-bulb; water 15 °C in / 21 °C out.
  3. Airflow 8,000 m³/h for VCA030, 25,000 m³/h for VCA120, 51,000 m³/h for VCA250.
  4. Reheat capacity 6 to 15 kW; humidification capacity 5 to 10 kg/h.
  5. Dimensions: depth 995 mm, height 1,975 mm; width 850 to 3,300 mm.
  6. More than 20% energy saving in downflow configuration versus conventional installation.
  7. 10-inch touchscreen, RS485 and SNMP, group control of up to 64 units, over 2,000 records.
  8. Air supply modes: upflow, top front with plenum and downflow.

Using it in design

  • Rating conditions are high return air (35 °C) with 15/21 °C water; have capacity recalculated at your own design conditions.
  • Carry unit width (850-3,300 mm) and 995 mm depth, with service clearances, into the hall layout.
  • Check cold aisle or plenum supply against airflow for downflow or ducted upflow options.
  • Write SNMP and RS485 interfaces, rotation and group control (up to 64 units) into the BMS control specification.
  • Add dual power supply modules and surge protectors to the power architecture specification.

Who should read it

Mechanical designers selecting chilled-water precision air conditioners for large server rooms.

Document contents

  1. High efficiency and energy saving
  2. High safety and reliability
  3. Intelligent control
  4. Flexible configuration
  5. Specifications

Publication details

Authors
INVT
Publisher
INVT
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

INVT (2026). INVT VCA Series Large Server Room Chilled-Water Precision Air Conditioner. INVT. https://www.invt.com/products/vca-room-chilled-water-precision-air-conditioner-294

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.