Technical guideFree to read2021

Cogeneration, Cooling and Ventilation (Birlikte Üretim, Soğutma ve Havalandırma)

Original title Birlikte Üretim, Soğutma ve Havalandırma

İSKİD / Birol Kılkış · Birol Kılkış

A 2021 İSKİD seminar presentation by Prof. Birol Kılkış that compares cogeneration and trigeneration cases by first- and second-law efficiency and proposes RUE and RUEX instead of PUE for data centres.

On this page

Overview

The presentation was prepared for an İSKİD seminar on cooling and ventilation in cogeneration systems in 2021 and runs to 19 slides. It starts with a base case that produces only power and heat, giving a primary energy saving (PES) of about 42%. The same calculation falls to 33% when an absorption chiller is added to form trigeneration, which the author presents alongside the argument that rising cooling loads will increase demand for trigeneration.

Four trigeneration arrangements are then compared: cogeneration with an absorption chiller, cogeneration with an ORC and an adsorption chiller, the same with a ground-source heat pump added, and a storage-based case using hydrogen, electrolysis and a fuel cell. Each shows first-law efficiency, second-law (exergy) efficiency and a recovery index, which rises from 1.0 in the base case to 1.7. The comparison axes are listed as CO2, cost and efficiency.

In the data-centre section the author argues that PUE relates a facility's electricity to its internal load but does not ask where the energy came from or how it was converted. Resource use effectiveness (RUE) and its exergy-based form RUEX are proposed instead. The worked examples on the slides give RUE 1.39 and RUEX 1.93 for cogeneration, and RUE 0.82 and RUEX 1.95 for the advanced trigeneration case.

This is seminar material: reasoning and formulas stay at slide level, without detailed derivation or validation. Energy storage for meeting cooling demand is a separate heading, with an ice-tank peak-shaving example and an hourly summer cooling load profile for a building. A modular data centre, the METU MATPUM building, the Kızılay vaccine building and a LEED platinum building appear as example projects.

Key points

  1. The base cogeneration case shows a primary energy saving (PES) of 42%; the trigeneration case with an absorption chiller shows 33%.
  2. Recovery indices for the four trigeneration arrangements are 1.3 (CHP+ABS), 1.4 (CHP+ORC+ADS), 1.6 (CHP+ORC+GSHP+ADS) and 1.7 (hydrogen, fuel cell and ADS); the base case is 1.0.
  3. First-law efficiency ranges from 0.35 to 0.75 and second-law efficiency from 0.35 to 0.55 across the cases.
  4. RUE asks where the consumed energy came from and which conversions it passes through inside the data centre; RUEX is its exergy-based form and is proposed as an alternative to PUE.
  5. In the worked example, cogeneration gives RUE 1.39 and RUEX 1.93; advanced trigeneration gives RUE 0.82 and RUEX 1.95.
  6. The advanced trigeneration example also computes the CO2 effect; the slide result is -2.5 kg CO2/kWh.
  7. Energy storage (ice tank, superheated and hot water tanks, electrolysis to hydrogen) is treated as a separate design topic for cooling solutions.
  8. The cooling side shows heat pumps (a cycle drawn with COP above 10), ORC and heat-driven chillers side by side as alternative cycles.

Using it in design

  • At a site with waste heat or cogeneration heat, compare heat-driven (absorption or adsorption) cooling against mechanical cooling using first- and second-law efficiency.
  • Report a resource-use indicator such as RUE next to PUE so that renewable and fuel-based supply chains can be told apart.
  • Size storage such as an ice tank or chilled-water store against the hourly load profile to cut peak cooling demand.
  • Build a decision matrix that compares trigeneration options on CO2 and cost as well as efficiency.
  • Do not take the slide values as design inputs; recompute with your own site temperature levels and efficiencies.

Who should read it

Energy and mechanical designers considering cogeneration, waste-heat recovery or alternative energy sources for data-centre cooling.

Document contents

  1. Combined heat and power (base case)
  2. Trigeneration: CHP and absorption chiller
  3. Trigeneration: ORC, GSHP and adsorption chiller
  4. Hydrogen, fuel cell and adsorption cooling
  5. Different methods in cooling
  6. Data centres: RUE instead of PUE
  7. Example projects
  8. Importance of energy storage
  9. Trigeneration worked examples

Publication details

Authors
Birol Kılkış
Publisher
İSKİD / Birol Kılkış
Year
2021
Document number
Kojenerasyon Sistemlerinde Soğutma ve Havalandırma semineri sunumu
Document language
Turkish
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Yayıncının açık PDF dosyası okundu. Açık erişim yeniden dağıtım izni anlamına gelmez; yalnızca künye, özgün kısa özet ve sayfa atıfları kaydedildi. PDF s. 1: © Birol Kılkış, 2021, tüm hakları saklıdır. ASHRAE üyeliği yazar unvanıdır; bu belge ASHRAE yayını olarak sunulmamıştır. Göstergeler yazarın önerisidir.

Citation

Birol Kılkış (2021). Birlikte Üretim, Soğutma ve Havalandırma. İSKİD / Birol Kılkış. Kojenerasyon Sistemlerinde Soğutma ve Havalandırma semineri sunumu. https://iskid.org.tr/wp-content/uploads/2021/06/BIROL-KILKIS_SUNUM.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.