White paperFree to read2025

White Paper on the Safety of Lithium-ion Battery Applications in Data Centres

Original title White Paper on the Safety of lithium-ion battery applications in data centres

International Telecommunication Union (ITU) and Huawei Digital Power Technologies Co., Ltd. · Paolo Gemma, Wei Liu et al.

An ITU and Huawei white paper of May 2025: a single battery room of at most 600 kWh, structure fire resistance of at least 2 hours, emergency ventilation of at least 12 air changes per hour, gas alarm at 10% and action at 25% LFL.

On this page

Overview

The white paper was prepared with ITU-T Study Group 5 and Huawei Digital Power, with authors from Alibaba Cloud, China Unicom, China Telecom and China Mobile. Its starting point is that lithium-ion batteries keep reacting after thermal runaway, releasing hot, toxic, combustible and explosive gases. It stresses that indirect losses from data-centre accidents caused by battery fires are far greater than the direct economic loss of the fire, and encourages stakeholders to adopt fire safety measures and technologies that raise intrinsic safety.

The content follows the life cycle: battery types and selection (cathode material and packaging), intrinsic safety requirements at cell, module and system level, fire safety, transportation, installation, operation and maintenance, emergency plan and drills, fire rescue and conclusions. The fire safety section covers fire characteristics, general requirements, layout, automatic extinguishing, ventilation and smoke exhaust, thermal runaway detection and alarm, drainage, emergency power off (EPO) and explosion protection and pressure relief.

Layout priorities are set: remote skid-mounted deployment in an independent container or cabinet is preferred, an independent structure is an alternative, and if neither is possible an independent room against the exterior wall of the building housing the main equipment room is used. For remote deployment, a fire resistance of at least 1 hour calls for 3 m or more to other buildings, and a 2 hour opposite wall with 1 hour other sides calls for 1 m or more. A room inside the building may not be in a basement and must be isolated from cable trays, air conditioning ducts and smoke exhaust ducts.

Detection and ventilation criteria are specific. The room must have at least one type of combustible gas detector, with at least two of each type; carbon monoxide and hydrogen detectors are recommended. Related standards require an alarm threshold of 10% LFL and an action threshold of 25% LFL. The paper calls for developing comprehensive international standards and notes that ITU could prepare complementary guidelines on recycling and end-of-life management.

Key points

  1. A single lithium-ion battery room inside a data-centre building should not exceed 600 kWh; it should be against an exterior wall and not in a basement or semi-basement.
  2. Room beams, columns, walls and sealed holes at least 2 hours fire rated, top and bottom floors at least 1.5 hours, evacuation door at least 1.5 hours.
  3. Remote deployment: at least 1 hour fire resistance calls for 3 m or more to other structures; a 2 hour opposite wall with 1 hour other sides calls for 1 m or more.
  4. Emergency ventilation of at least 12 air changes per hour with explosion-proof fans and a manual exhaust switch outside the room.
  5. With gaseous extinguishing the emergency fan stops after discharge; with water spray, sprinkler or water mist the fan keeps running.
  6. Combustible gas alarm threshold 10% LFL, action (ventilation) threshold 25% LFL; hydrogen or carbon monoxide measured, at least 2 detectors of each type per room.
  7. In thermal runaway hydrogen, carbon monoxide and a small amount of hydrogen fluoride are released; no combustible gas forms in normal operation.
  8. Hydrogen detectors go on the ceiling and carbon monoxide detectors near the battery cabinet; fire dampers must have an operating temperature of at least 150 degrees C.
  9. Maintenance defines routine, monthly, quarterly and annual inspection levels; emergency plan and drill requirements are given.

Using it in design

  • Plan the battery room remote from the main hall in an independent container or structure where possible; if in the building, use an exterior-wall room outside the basement, with a single room limited to 600 kWh.
  • Rate the battery room structure for 2 hours, floors for 1.5 hours and the door for 1.5 hours, and isolate it from cable trays, air conditioning and smoke exhaust ducts.
  • Design emergency ventilation at 12 or more air changes per hour with explosion-proof fans, tied to a two-stage gas alarm at 10% and 25% LFL, with separate fan logic for gaseous and water-based extinguishing.
  • Place at least two hydrogen or carbon monoxide detectors in each battery room and link them to the ventilation and fire alarm systems.
  • Add the routine, monthly, quarterly and annual inspection checklists and the emergency drill programme to the operations manual.

Who should read it

Electrical and fire engineers designing data-centre UPS battery rooms, operators and standards developers.

Document contents

  1. Introduction
  2. Terminology and abbreviation
  3. Overview of data centre lithium-ion batteries
  4. Intrinsic safety requirements for data centre lithium-ion battery systems
  5. Fire safety requirements for data centre lithium-ion batteries
  6. Transportation safety requirements
  7. Installation requirements
  8. Operation and maintenance requirements
  9. Emergency plan and drill
  10. Fire rescue and emergency handling
  11. Conclusions and future directions: the critical role of international standards

Related standards

  • NFPA 855
  • UL 9540A
  • IEC 62619
  • IEC 62485-5

Publication details

Authors
Paolo Gemma; Wei Liu; Zhenghai Liu; Ying Shi; Lifeng Sun; Reyna Ubeda; Xiaojian Ye; Lei Zhang; Yu Zhang
Publisher
International Telecommunication Union (ITU) and Huawei Digital Power Technologies Co., Ltd.
Year
2025
Document number
ISBN 978-92-61-40211-2
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
CC BY-NC-SA 3.0: share with attribution for noncommercial purposes under the same licence
Original licence note

Copyright page: 'available under the Creative Commons Attribution-NonCommercial-ShareAlike 3.0 IGO licence'; NonCommercial, so treated as link-only for a commercial product.

Citation

Paolo Gemma; Wei Liu; Zhenghai Liu; Ying Shi; Lifeng Sun; Reyna Ubeda; Xiaojian Ye; Lei Zhang; Yu Zhang (2025). White Paper on the Safety of lithium-ion battery applications in data centres. International Telecommunication Union (ITU) and Huawei Digital Power Technologies Co., Ltd.. ISBN 978-92-61-40211-2. https://digitalpower.huawei.com/dam/asset/view/f5840fba7aac47abb12bdccfda0f0cf8.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.