Methods for Improving Data Centers Energy Efficiency (Veri Merkezlerinde Enerji Verimliliğini Arttırıcı Yöntemler)
Original title Veri Merkezlerinde Enerji Verimliliğini Arttırıcı Yöntemler
İstanbul Teknik Üniversitesi · Emre Şen
A 2019 master's thesis at Istanbul Technical University's Energy Institute: in a 720 kW IT case study, a modular UPS with temperature-controlled closed cooling gives PUE 1.34, against 1.39 for pressure-controlled cooling with a monoblock UPS.
On this page
Overview
Emre Sen's thesis addresses the three main elements that set data-centre electricity use and continuity: UPS systems, cooling systems and PDUs. It first introduces the general structure of a data centre, the PUE concept, UPS operating modes (double conversion, battery, static bypass), generator integration and conventional air, glycol and water cooled systems. The efficiency-raising choices are then tested on real test rigs and in a case study of a project in Turkey.
The UPS part compares modular and monoblock UPS, load-matched sizing, topology selection, and conventional versus enhanced eco mode. On a test rig of about 1 MW the measured efficiencies are 96.7% in double conversion, 98.7% in conventional eco mode and 97.6% in enhanced eco mode. The thesis tries to overturn the perception that eco mode is unreliable and recommends enhanced eco mode for high efficiency.
The cooling part compares closed smart cooling, pressure-controlled and temperature-controlled. Because the cold aisle is fully isolated from hot air, the cooling unit's supply temperature can be held higher than the 14-18 degrees C of a conventional system, and fan energy falls. In the case study the temperature-controlled system saves 139,893 kWh a year (53%) and 100,723 TL; the modular UPS saves 55,292 EUR in first cost, 68,920 EUR in 10-year operating cost and 454,110 TL in 10-year UPS losses.
The case rests on a 1200 kVA modular UPS of 3 modules with a 720 kW IT load and 70 kW non-IT load; two modules carry the load and the third is redundant. This is a master's thesis, its calculations rest on one project and specific manufacturers' equipment, and the cost figures reflect 2019 market conditions. As a Turkish source it gives a numerical example of PUE, UPS and closed-aisle cooling choices.
Key points
- In the case study PUE is 1.34 with temperature-controlled closed cooling and a modular UPS, and 1.39 with pressure-controlled cooling and a monoblock UPS.
- Temperature-controlled cooling saves 139,893 kWh a year (53%) and 100,723 TL in energy cost over the pressure-controlled option.
- The modular UPS saves 55,292 EUR in first cost, 68,920 EUR in 10-year total operating cost and 454,110 TL in 10-year UPS losses over the monoblock option.
- On the test rig UPS efficiency is 96.7% in double conversion, 98.7% in conventional eco mode and 97.6% in enhanced eco mode (the catalogue figure for enhanced eco is 98%).
- The proposed modular UPS is 1200 kVA made of 3 power modules; 2 modules carry the 720 kW IT and 70 kW non-IT load and 1 is redundant; batteries are 9 strings, each of 44 VRLA units of 93 Ah.
- In a closed system cold air does not mix with hot air, so for a 20-25 degrees C IT environment the unit outlet can be held higher than the 14-18 degrees C of a conventional system.
- Reducing EC fan speed cuts power demand sharply; the thesis recommends selecting cooling units to run at part capacity rather than sizing the count to the full heat load.
- The thesis notes that PUE ranges from 1 to 2 and that Tier IV corresponds to 99.995% annual availability.
Using it in design
- When selecting UPS, compare modular and monoblock options on 10-year operating and loss cost, not first cost alone; in the case the modular design wins on all counts.
- Size the UPS to the load: efficiency falls as load fraction falls; provide N+1 redundancy through module count (in the example 2 modules carry the load and 1 is spare).
- Before using eco or enhanced eco mode, verify output voltage and transfer characteristics with the manufacturer's test data.
- In closed-aisle cooling, select a number of cooling units that runs at part capacity rather than full load, and compute the saving from the EC fan speed curve.
- Include UPS losses, cooling consumption, PDU losses and non-IT loads in the PUE calculation, and compare design alternatives with the same method.
Who should read it
Design engineers selecting data-centre UPS and cooling, energy-efficiency analysts, and graduate students looking for a Turkish source.
Document contents
- Introduction
- Data centers (overview, structure, PUE, power systems, conventional cooling)
- Increasing energy efficiency in data centers (UPS selection, operating mode, topology, cooling, PDU)
- Case study (cooling method, UPS system design, cost analysis, PDU, PUE calculation)
- Conclusion and recommendations
Publication details
- Authors
- Emre Şen
- Publisher
- İstanbul Teknik Üniversitesi
- Year
- 2019
- Document number
- Yüksek lisans tezi, Enerji Enstitüsü, Haziran 2019
- Document language
- Turkish
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official publisher or university publicly accessible text; no open redistribution licence established. Repository dateissued link differs from the June 2019 cover month; bibliographic year is consistently 2019. Repository explicitly prohibits reproduction/distribution without written permission.
Citation
Emre Şen (2019). Veri Merkezlerinde Enerji Verimliliğini Arttırıcı Yöntemler. İstanbul Teknik Üniversitesi. Yüksek lisans tezi, Enerji Enstitüsü, Haziran 2019. https://polen.itu.edu.tr/bitstreams/fedf988b-c3b9-4cb2-8a38-adb811fca8e4/download
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.