Data-centre Energy Efficiency: New Measures Effective April 2026
Original title Data-centre energy efficiency: new measures effective April 2026
Japan Agency for Natural Resources and Energy (METI)
Japan Agency for Natural Resources and Energy (METI): the existing benchmark objective is PUE of 1.4 or less by FY2030, and new facilities established from FY2029 are expected to reach PUE of 1.3 or less from the fiscal year after two years of operation.
On this page
Overview
The official explanation from Japan's Agency for Natural Resources and Energy describes the expanded data-centre reporting and efficiency framework. It includes operator categories and a phased target for new facilities. It separates the existing benchmark objective from the new construction requirement: the existing benchmark is PUE of at most 1.4 by FY2030, while new facilities established from FY2029 are expected to meet PUE of at most 1.3 from the fiscal year after two years of operation.
The expansion adds hosting and cloud tenant operators to the housing and owner categories. The measures apply from April 2026. For operators planning new facilities and reporting obligations, the source settles which PUE thresholds apply from which dates and to which groups of facilities.
Key points
- Existing benchmark objective: PUE of 1.4 or less by FY2030.
- New facilities established from FY2029 are expected to meet PUE of 1.3 or less from the fiscal year after two years of operation.
- The framework covers hosting and cloud tenant operators in addition to housing and owner categories.
- The new measures apply from April 2026.
- The existing benchmark objective and the new construction requirement are separate provisions.
Using it in design
- For facilities commissioned in Japan after FY2029, treat PUE of 1.3 or less as a design criterion based on measurement after the second year of operation.
- For existing facilities, make PUE of 1.4 or less for FY2030 the reference of the efficiency improvement plan.
- For organisations acting as tenant or cloud operators, check by operator category whether the reporting obligation applies.
- Settle PUE measurement points and the reporting method at design stage.
Who should read it
Teams designing and operating data centres in Japan, tenant operators and energy compliance advisers.
Publication details
- Authors
- Japan Agency for Natural Resources and Energy (METI)
- Publisher
- Japan Agency for Natural Resources and Energy (METI)
- Year
- 2026
- Document language
- Japanese
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official Japanese explanatory article dated 20 May 2026, correction note 4 June 2026. Linked detailed guideline PDF was inaccessible; this entry summarizes the opened article only.
Citation
Japan Agency for Natural Resources and Energy (METI) (2026). Data-centre energy efficiency: new measures effective April 2026. Japan Agency for Natural Resources and Energy (METI). https://www.enecho.meti.go.jp/about/special/johoteikyo/data_center2026.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.