Cascade Cooling: Combining Dry & Wet Cooling to Reduce Energy and Water Consumption
Original title Cascade Cooling - Combining Dry & Wet Cooling to reduce energy and water consumption
Kelvion
Kelvion Cascade Cooling pipes dry coolers in series with cooling towers through plate heat exchangers, with a 2 K approach to wet bulb and free-cooling, mixed and mechanical modes.
On this page
Overview
Kelvion's factsheet, dated late 2025, describes a heat rejection arrangement that combines dry and wet cooling technologies. It targets heat rejection for liquid-cooled chillers (LCC), mainly for data centres and power plants and for heavy and light industry. A dry mode serves the cooler months, a wet mode gives maximum capacity at summer peak and a mixed mode bridges the two.
There are three operating modes. Free cooling runs at low ambient temperature with no mechanical cooling, using two dry coolers and one plate heat exchanger (PHE). Mixed mode at medium ambient rejects the liquid-cooled chillers' heat through dry coolers, plate heat exchangers and cooling towers. Mechanical mode at high ambient runs power- or water-conserving and gives high peak safety. Process fluid flows in series from dry cooler to cooling tower.
The document states a 2 K approach to wet bulb through the plate heat exchangers, against 4-5 K for adiabatic or hybrid V-bank coolers. Adiabatic efficiency is stated as up to 100% (95% for hybrid V-bank). Dry coolers are sized for reduced water and towers for peak load, and the operator can set a water-use preference. Poor-quality or sea water can be used on the tower side. The document is promotional and gives no sizing data.
Key points
- Three modes: free cooling (low ambient), mixed (medium) and mechanical (high).
- Free cooling uses two dry coolers and one plate heat exchanger; mechanical mode brings in chillers and cooling towers.
- Plate heat exchanger approach of 2 K to wet bulb; 4-5 K for adiabatic/hybrid V-bank.
- Adiabatic efficiency up to 100%; 95% for adiabatic/hybrid V-bank.
- Process fluid flows in series from dry cooler to cooling tower.
- Dry coolers are sized for reduced water and towers for peak load.
- Poor water quality or sea water can be used on the tower side.
- Mega-Bay and Giga-Bay tower series are cited for a high proportion of free cooling.
Using it in design
- Use the annual dry-bulb and wet-bulb distribution to calculate free, mixed and mechanical mode hours, and set the energy-versus-water preference from it.
- Carry the plate heat exchanger approach (2 K) into design water temperatures; it must fit the liquid-cooled chillers' outlet temperature target.
- Size dry cooler capacity for the water saving target and tower capacity for peak load separately.
- For poor water quality or coastal sites, choose suitable materials on the tower side.
- Define the control logic for mode changeover and valve sequencing in the specification.
Who should read it
Mechanical engineers designing heat rejection for data centres and power plants, and decision makers balancing water and energy use.
Document contents
- Cascade Cooling overview
- Main features
- Free cooling, mixed mode and mechanical mode
- Key features
Publication details
- Authors
- Kelvion
- Publisher
- Kelvion
- Year
- 2025
- Document number
- Version 01 12/25
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document