Technical guideFree to read2025

Cascade Cooling: Combining Dry & Wet Cooling to Reduce Energy and Water Consumption

Original title Cascade Cooling - Combining Dry & Wet Cooling to reduce energy and water consumption

Kelvion

Kelvion Cascade Cooling pipes dry coolers in series with cooling towers through plate heat exchangers, with a 2 K approach to wet bulb and free-cooling, mixed and mechanical modes.

On this page

Overview

Kelvion's factsheet, dated late 2025, describes a heat rejection arrangement that combines dry and wet cooling technologies. It targets heat rejection for liquid-cooled chillers (LCC), mainly for data centres and power plants and for heavy and light industry. A dry mode serves the cooler months, a wet mode gives maximum capacity at summer peak and a mixed mode bridges the two.

There are three operating modes. Free cooling runs at low ambient temperature with no mechanical cooling, using two dry coolers and one plate heat exchanger (PHE). Mixed mode at medium ambient rejects the liquid-cooled chillers' heat through dry coolers, plate heat exchangers and cooling towers. Mechanical mode at high ambient runs power- or water-conserving and gives high peak safety. Process fluid flows in series from dry cooler to cooling tower.

The document states a 2 K approach to wet bulb through the plate heat exchangers, against 4-5 K for adiabatic or hybrid V-bank coolers. Adiabatic efficiency is stated as up to 100% (95% for hybrid V-bank). Dry coolers are sized for reduced water and towers for peak load, and the operator can set a water-use preference. Poor-quality or sea water can be used on the tower side. The document is promotional and gives no sizing data.

Key points

  1. Three modes: free cooling (low ambient), mixed (medium) and mechanical (high).
  2. Free cooling uses two dry coolers and one plate heat exchanger; mechanical mode brings in chillers and cooling towers.
  3. Plate heat exchanger approach of 2 K to wet bulb; 4-5 K for adiabatic/hybrid V-bank.
  4. Adiabatic efficiency up to 100%; 95% for adiabatic/hybrid V-bank.
  5. Process fluid flows in series from dry cooler to cooling tower.
  6. Dry coolers are sized for reduced water and towers for peak load.
  7. Poor water quality or sea water can be used on the tower side.
  8. Mega-Bay and Giga-Bay tower series are cited for a high proportion of free cooling.

Using it in design

  • Use the annual dry-bulb and wet-bulb distribution to calculate free, mixed and mechanical mode hours, and set the energy-versus-water preference from it.
  • Carry the plate heat exchanger approach (2 K) into design water temperatures; it must fit the liquid-cooled chillers' outlet temperature target.
  • Size dry cooler capacity for the water saving target and tower capacity for peak load separately.
  • For poor water quality or coastal sites, choose suitable materials on the tower side.
  • Define the control logic for mode changeover and valve sequencing in the specification.

Who should read it

Mechanical engineers designing heat rejection for data centres and power plants, and decision makers balancing water and energy use.

Document contents

  1. Cascade Cooling overview
  2. Main features
  3. Free cooling, mixed mode and mechanical mode
  4. Key features

Publication details

Authors
Kelvion
Publisher
Kelvion
Year
2025
Document number
Version 01 12/25
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

© Kelvion, All rights reserved (pp. 1-2)

Citation

Kelvion (2025). Cascade Cooling - Combining Dry & Wet Cooling to reduce energy and water consumption. Kelvion. Version 01 12/25. https://d2xjeen3zaup4u.cloudfront.net/asset/767398133948/document_vqlhpsghfd7cdalqnftgtdt35k/PF_HRR_CascadeCooling_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.