Research paperFree to read2026

Experimental investigation on operating strategies of a cooling system combined phase change cold storage with evaporation for data centers

Journal of Building Engineering / Kingston University London · Zhangqin Yang, Zujing Zhang et al.

A 2026 experimental study in the Journal of Building Engineering finds that placing the direct evaporative module in the middle of the phase change segment cuts pump energy by over 75% and water use by 8-25% against conventional direct evaporative cooling.

On this page

Overview

Phase change cold storage extends the application range of direct evaporative cooling and makes year-round free cooling possible in some regions. The work by researchers from Kingston University London, Guizhou University, Hong Kong Polytechnic University and other institutions addresses the limited literature on jointly optimising the layout of the direct evaporation module and spray flow prediction.

The experiments compare two combined systems with direct evaporative cooling at the front and in the middle of the phase change segment. A sensitivity analysis on the middle system then covers inlet temperature and humidity, spray flow rate and wind speed, and a spray flow prediction model is developed. Outlet temperature is found to correlate quadratically with inlet temperature and linearly with the other parameters.

Key points

  1. At 32 degrees C, 40% relative humidity and 1.6 m/s wind speed, both systems keep outlet air below 27 degrees C and 80% relative humidity, with the middle system giving the highest energy efficiency ratio.
  2. At 32 degrees C inlet temperature and 0.08 L/min spray flow, the supply air requirement is not met if inlet relative humidity exceeds 45% or wind speed exceeds 2 m/s.
  3. Outlet temperature correlates quadratically with inlet temperature and linearly with the other parameters.
  4. Outlet relative humidity correlates linearly with inlet humidity and quadratically with the other parameters.
  5. The middle system reduces pump energy by more than 75% and water consumption by 8-25% against conventional direct evaporative cooling.

Using it in design

  • In designs combining free cooling with evaporative cooling, assess whether placing the evaporative module in the middle of the phase change segment saves pump energy and water.
  • Compare inlet humidity and air velocity limits at design conditions (45% and 2 m/s in the example) with the required supply air.
  • Provide a control strategy that varies spray flow with inlet conditions.
  • In water-constrained regions, add the water saving rate to the system selection criteria.

Who should read it

Mechanical engineers and researchers designing free cooling and evaporative cooling systems.

Publication details

Authors
Zhangqin Yang; Zujing Zhang; Jiri Zhou; Jianxing Liao; Xiaoyan Yi; Xing Liang; Hongwei Wu; Ruiyong Mao; Yang Lei
Publisher
Journal of Building Engineering / Kingston University London
Year
2026
Document number
132, 117438
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official publisher or author-institution source opened. No general redistribution permission established; metadata and original short summaries only.

Citation

Zhangqin Yang; Zujing Zhang; Jiri Zhou; Jianxing Liao; Xiaoyan Yi; Xing Liang; Hongwei Wu; Ruiyong Mao; Yang Lei (2026). Experimental investigation on operating strategies of a cooling system combined phase change cold storage with evaporation for data centers. Journal of Building Engineering / Kingston University London. 132, 117438. https://doi.org/10.1016/j.jobe.2026.117438

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.