Research paperPDF2022

Study on Thermal Runaway Propagation Characteristics of Lithium Iron Phosphate Battery Pack under Different SOCs

Electronics (MDPI AG) · Minghao Zhu, Jiajie Yao et al.

Three 42 Ah prismatic LFP cells in a row were driven into thermal runaway by a 1500 W heating plate against the first cell at 100%, 50% and 0% state of charge; higher SOC gave hotter, faster runaway and much shorter delays between neighbouring cells.

CC BY 4.0: share with attribution

On this page

Overview

The study asks how state of charge (SOC) changes the way thermal runaway propagates through an LFP battery pack. Three 42 Ah prismatic LFP cells (about 917 g each) were placed in a row with a 1500 W copper heating plate against cell 1, and temperatures, heating rates, mass loss and venting behaviour were recorded at 100%, 50% and 0% SOC.

At 100% SOC the first safety valve ruptured after 1791 s of heating with the plate at 265 °C, and runaway followed about 6 s later. The runaway interval was 7 s from cell 1 to cell 2 and 37 s from cell 2 to cell 3. Compared with 50% SOC, the cell 1→2 interval at 100% SOC was 71.4% shorter and the cell 2→3 interval 87.2% shorter. At 100% SOC the runaway neighbour supplied 71.6% of the heat absorbed by cell 2 and 89.9% of that absorbed by cell 3 (68.6% and 77.9% at 50% SOC), so most of the heat pushing downstream cells into runaway came from the runaway neighbour rather than the external heater.

The 100% SOC pack ejected sparks when the safety valve ruptured; the 50% and 0% SOC packs only produced smoke, and the 0% SOC pack's overall temperature rise rate stayed below 1 °C/s. Under the same SOC, runaway behaviour of cells 1 and 2 was more intense than cell 3, with maximum temperature, temperature rise rate and mass change rate ordered cell 1 > cell 2 > cell 3.

Limits: one cell type, only three cells and a one-sided heating plate; thermal barriers, cooling and larger cell arrays in real modules were not examined. The conclusion is that pack fire and explosion risk rises with SOC, and runaway is more intense closer to the heat source.

Key points

  1. Test cells were 42 Ah prismatic LFP cells (about 917 g each), arranged three in a row with a 1500 W copper heating plate against cell 1.
  2. At 100% SOC the first safety valve ruptured after 1791 s of heating, with the plate at 265 °C, and runaway followed about 6 s later.
  3. At 100% SOC the runaway interval was 7 s from cell 1 to cell 2 and 37 s from cell 2 to cell 3.
  4. Compared with 50% SOC, the cell 1→2 interval at 100% SOC was 71.4% shorter and the cell 2→3 interval 87.2% shorter.
  5. At 100% SOC, the runaway neighbour supplied 71.6% of the heat absorbed by cell 2 and 89.9% of that absorbed by cell 3 (68.6% and 77.9% at 50% SOC).
  6. The 100% SOC pack ejected sparks when the safety valve ruptured; the 50% and 0% SOC packs only produced smoke, and the 0% SOC pack's overall temperature rise rate stayed below 1 °C/s.

Using it in design

  • In inter-cell thermal barrier design for battery modules, base the design on the thermal contribution of the runaway neighbour (70-90%); neighbour-to-neighbour heat, not an external source, drives propagation.
  • Consider limiting SOC (for example during storage or maintenance) as an operating control for propagation risk; at 0% SOC the temperature rise rate stayed below 1 °C/s.
  • Take spark ejection at high SOC into account in fire and explosion protection design (vent direction, distance to combustible material).

Who should read it

Engineers assessing safety and thermal runaway propagation of LFP battery packs, UPS batteries and BESS.

Document contents

  1. 1. Introduction
  2. 2. Experiment (2.1 Battery, 2.2 Experimental Device and Battery Modules Description, 2.3 Experiment Setup)
  3. 3. Results and Discussion (temperature and safety venting comparisons, 3.2 Quality Analysis of TR and Its Propagation, 3.3 LFP Battery TR Behavior Analysis)
  4. 4. Conclusions

Related standards

  • UL 9540A
  • NFPA 855

Read the document

lfp-pack-thermal-runaway-soc-propagation-2022.pdf

PDF · 3.1 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Minghao Zhu; Jiajie Yao; Feiyu Qian; Weiyi Luo; Yin Chen; Luyao Zhao; Mingyi Chen
Publisher
Electronics (MDPI AG)
Year
2022
Volume
12
Issue
1
Pages
200
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
www.mdpi.com
Original licence note

PDF p.1 states the article is distributed under the terms of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). Published online 31 December 2022 in volume 12 (2023).

Citation

Minghao Zhu; Jiajie Yao; Feiyu Qian; Weiyi Luo; Yin Chen; Luyao Zhao; Mingyi Chen (2022). Study on Thermal Runaway Propagation Characteristics of Lithium Iron Phosphate Battery Pack under Different SOCs. Electronics (MDPI AG). 12(1), 200. https://doi.org/10.3390/electronics12010200

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.