Research paperPDF2026

Techno-Economic Comparison of Data Center Cooling Using Magnetic Bearing Chillers and Aquifer Thermal Energy Storage

Energies (MDPI AG) · Apurva Malpure, Andrew Stumpf et al.

An hourly techno-economic comparison of three chilled-water plants for the same data-centre IT load profile: a water-cooled centrifugal chiller baseline, magnetic-bearing chillers (MBC), and MBC with a screening-level aquifer thermal energy storage (ATES) discharge.

CC BY 4.0: share with attribution

On this page

Overview

Data centres are large and rapidly growing electricity consumers, and cooling systems account for a substantial share of their energy demand. The study presents a climate-sensitive, hourly techno-economic comparison of three cooling configurations under consistent operating assumptions. All share a waterside economiser and two 4058 kW chillers, and Phoenix and Fairbanks bracket US cooling climates. The plant uses 7 °C chilled-water supply with a 5 K delta-T, and a cooling tower with a 4 K approach and a 2 °C minimum condenser-water temperature.

Phoenix baseline operating modes: 204 h full free cooling, 1748 h partial free cooling and 6808 h mechanical only; Fairbanks: 5350 h, 1297 h and 2113 h. MBC cut annual cooling electricity from 1169.4 to 957.4 MWh in Phoenix (18.1%) and from 361.6 to 319.4 MWh in Fairbanks (11.7%). Cooling-only PUE' was 1.095 (baseline) and 1.078 (MBC) in Phoenix, and 1.029 and 1.026 in Fairbanks.

With a premium capex of USD 123,527, MBC paid back in 5.8 years in Phoenix but 36.6 years in Fairbanks. Peak cooling demand fell by 119.4 kW and 71.6 kW respectively. MBC+ATES gave no extra electricity savings over MBC-only, and its better discounted savings disappear (NPV negative) if its O&M is set equal to MBC-only.

Limits: the authors stress that the ATES case is a simplified screening scenario and that results depend on tariff and O&M assumptions; ATES should not be read as a complete seasonal design or full techno-economic assessment. Only two climates were examined.

Key points

  1. The plant uses 7 °C chilled-water supply with a 5 K delta-T, and a cooling tower with a 4 K approach and a 2 °C minimum condenser-water temperature; tower water temperature = max(outdoor wet-bulb + approach, minimum).
  2. Phoenix baseline operating modes: 204 h full free cooling, 1748 h partial free cooling and 6808 h mechanical only; Fairbanks: 5350 h, 1297 h and 2113 h.
  3. MBC cut annual cooling electricity from 1169.4 to 957.4 MWh in Phoenix (18.1%) and from 361.6 to 319.4 MWh in Fairbanks (11.7%).
  4. Cooling-only PUE' was 1.095 (baseline) and 1.078 (MBC) in Phoenix, and 1.029 and 1.026 in Fairbanks.
  5. With a premium capex of USD 123,527, MBC paid back in 5.8 years in Phoenix but 36.6 years in Fairbanks; peak cooling demand fell by 119.4 kW and 71.6 kW.
  6. MBC+ATES gave no extra electricity savings over MBC-only; its better discounted savings disappear (NPV negative) if its O&M is set equal to MBC-only.

Using it in design

  • Evaluate magnetic-bearing chiller investment by climate: payback was 5.8 years in a hot climate relying more on mechanical cooling, 36.6 years in a cold climate dominated by free cooling.
  • Model chiller staging and operating modes (full, partial free cooling, mechanical) hourly and report cooling-only PUE and peak demand.
  • Show storage-option savings such as ATES with sensitivity to O&M and tariff assumptions; NPV turned negative when O&M was equalised.

Who should read it

Designers and investment decision makers comparing chilled-water plant chiller technology and storage options techno-economically.

Document contents

  1. 1. Introduction
  2. 2. Materials and Methods (2.1 Assumptions and Boundary Conditions, 2.2 System Description, 2.3 Data Inputs and Parameters: weather and humidity data, IT load profile, indoor environmental conditions; 2.4 Chiller and Auxiliary Power Model, 2.5 ATES Dispatch and Storage Balance, 2.6 Hourly Simulation Workflow, 2.7 Financial Evaluation, 2.8 Model Verification and Quality Assurance)
  3. 3. Results (3.1 Energy Performance: operating modes, energy consumption and PUE'; 3.2 Economic Performance)
  4. 4. Discussion (4.1 Benchmarking Against Previous Studies, 4.2 Limitations and Future Work)
  5. 5. Conclusions

Related standards

  • ASHRAE 90.4
  • ASHRAE TC9.9 Thermal Guidelines

Read the document

magnetic-bearing-chiller-ates-dc-cooling-2026.pdf

PDF · 1.2 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Apurva Malpure; Andrew Stumpf; Upasana Pandey; Yu-Feng Lin; Craig Bradshaw
Publisher
Energies (MDPI AG)
Year
2026
Volume
19
Issue
17
Pages
3947
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
www.mdpi.com
Original licence note

p.1 states the article is open access under the Creative Commons Attribution (CC BY) licence.

Citation

Apurva Malpure; Andrew Stumpf; Upasana Pandey; Yu-Feng Lin; Craig Bradshaw (2026). Techno-Economic Comparison of Data Center Cooling Using Magnetic Bearing Chillers and Aquifer Thermal Energy Storage. Energies (MDPI AG). 19(17), 3947. https://doi.org/10.3390/en19173947

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.