Techno-Economic Comparison of Data Center Cooling Using Magnetic Bearing Chillers and Aquifer Thermal Energy Storage
Energies (MDPI AG) · Apurva Malpure, Andrew Stumpf et al.
An hourly techno-economic comparison of three chilled-water plants for the same data-centre IT load profile: a water-cooled centrifugal chiller baseline, magnetic-bearing chillers (MBC), and MBC with a screening-level aquifer thermal energy storage (ATES) discharge.
CC BY 4.0: share with attribution
On this page
Overview
Data centres are large and rapidly growing electricity consumers, and cooling systems account for a substantial share of their energy demand. The study presents a climate-sensitive, hourly techno-economic comparison of three cooling configurations under consistent operating assumptions. All share a waterside economiser and two 4058 kW chillers, and Phoenix and Fairbanks bracket US cooling climates. The plant uses 7 °C chilled-water supply with a 5 K delta-T, and a cooling tower with a 4 K approach and a 2 °C minimum condenser-water temperature.
Phoenix baseline operating modes: 204 h full free cooling, 1748 h partial free cooling and 6808 h mechanical only; Fairbanks: 5350 h, 1297 h and 2113 h. MBC cut annual cooling electricity from 1169.4 to 957.4 MWh in Phoenix (18.1%) and from 361.6 to 319.4 MWh in Fairbanks (11.7%). Cooling-only PUE' was 1.095 (baseline) and 1.078 (MBC) in Phoenix, and 1.029 and 1.026 in Fairbanks.
With a premium capex of USD 123,527, MBC paid back in 5.8 years in Phoenix but 36.6 years in Fairbanks. Peak cooling demand fell by 119.4 kW and 71.6 kW respectively. MBC+ATES gave no extra electricity savings over MBC-only, and its better discounted savings disappear (NPV negative) if its O&M is set equal to MBC-only.
Limits: the authors stress that the ATES case is a simplified screening scenario and that results depend on tariff and O&M assumptions; ATES should not be read as a complete seasonal design or full techno-economic assessment. Only two climates were examined.
Key points
- The plant uses 7 °C chilled-water supply with a 5 K delta-T, and a cooling tower with a 4 K approach and a 2 °C minimum condenser-water temperature; tower water temperature = max(outdoor wet-bulb + approach, minimum).
- Phoenix baseline operating modes: 204 h full free cooling, 1748 h partial free cooling and 6808 h mechanical only; Fairbanks: 5350 h, 1297 h and 2113 h.
- MBC cut annual cooling electricity from 1169.4 to 957.4 MWh in Phoenix (18.1%) and from 361.6 to 319.4 MWh in Fairbanks (11.7%).
- Cooling-only PUE' was 1.095 (baseline) and 1.078 (MBC) in Phoenix, and 1.029 and 1.026 in Fairbanks.
- With a premium capex of USD 123,527, MBC paid back in 5.8 years in Phoenix but 36.6 years in Fairbanks; peak cooling demand fell by 119.4 kW and 71.6 kW.
- MBC+ATES gave no extra electricity savings over MBC-only; its better discounted savings disappear (NPV negative) if its O&M is set equal to MBC-only.
Using it in design
- Evaluate magnetic-bearing chiller investment by climate: payback was 5.8 years in a hot climate relying more on mechanical cooling, 36.6 years in a cold climate dominated by free cooling.
- Model chiller staging and operating modes (full, partial free cooling, mechanical) hourly and report cooling-only PUE and peak demand.
- Show storage-option savings such as ATES with sensitivity to O&M and tariff assumptions; NPV turned negative when O&M was equalised.
Who should read it
Designers and investment decision makers comparing chilled-water plant chiller technology and storage options techno-economically.
Document contents
- 1. Introduction
- 2. Materials and Methods (2.1 Assumptions and Boundary Conditions, 2.2 System Description, 2.3 Data Inputs and Parameters: weather and humidity data, IT load profile, indoor environmental conditions; 2.4 Chiller and Auxiliary Power Model, 2.5 ATES Dispatch and Storage Balance, 2.6 Hourly Simulation Workflow, 2.7 Financial Evaluation, 2.8 Model Verification and Quality Assurance)
- 3. Results (3.1 Energy Performance: operating modes, energy consumption and PUE'; 3.2 Economic Performance)
- 4. Discussion (4.1 Benchmarking Against Previous Studies, 4.2 Limitations and Future Work)
- 5. Conclusions
Related standards
- ASHRAE 90.4
- ASHRAE TC9.9 Thermal Guidelines
Read the document
magnetic-bearing-chiller-ates-dc-cooling-2026.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Apurva Malpure; Andrew Stumpf; Upasana Pandey; Yu-Feng Lin; Craig Bradshaw
- Publisher
- Energies (MDPI AG)
- Year
- 2026
- Volume
- 19
- Issue
- 17
- Pages
- 3947
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
p.1 states the article is open access under the Creative Commons Attribution (CC BY) licence.
Citation
Apurva Malpure; Andrew Stumpf; Upasana Pandey; Yu-Feng Lin; Craig Bradshaw (2026). Techno-Economic Comparison of Data Center Cooling Using Magnetic Bearing Chillers and Aquifer Thermal Energy Storage. Energies (MDPI AG). 19(17), 3947. https://doi.org/10.3390/en19173947
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.