OmniA 40 F / 50 F / 65 F Operating Manual
Original title OmniA 40 F / 50 F / 65 F: Kullanım Kılavuzu
Masdaf
Bilingual manual for Masdaf OmniA 40 F, 50 F and 65 F high-efficiency circulation pumps: EEI ≤ 0.21, 0 to 110 °C fluid, four control modes, commissioning, maintenance and E01-E18 fault codes.
On this page
Overview
The manual gives installation, operating and maintenance instructions for Masdaf's OmniA series of flanged electronic circulation pumps, in Turkish and English. The pumps are designed for hot-water circulation in central heating, and the stated applications also include low-viscosity fluids in industrial and commercial use and solar thermal systems. It is specific to one product family and is not a general pump-selection guide.
According to the technical data table, the pump runs on 1×230 V, 50/60 Hz, with fluid temperature from 0 to +110 °C and ambient from 0 to +40 °C. Protection class is IP44, the energy efficiency index is EEI ≤ 0.21 and maximum operating pressure is 10 bar. Permitted fluids are heating water to VDI 2035 and a 1:1 water/glycol mixture. The manufacturer cites energy savings of up to about 80% against a conventional circulation pump.
On the control side there are constant speed (CS), constant pressure (CP), proportional pressure (PP) and an AUTO SmartAdapt mode intended for dual-circuit and underfloor heating systems. The pump ships in AUTO SmartAdapt, where adaptation can take more than a week. A model table lists the available levels per mode; for example the 40-18F-250 offers levels 1-5 in constant speed and 1-12 in constant and proportional pressure.
The safety and maintenance sections cover isolation, preventing re-energisation and waiting for a hot pump to cool. The fault table gives causes and remedies for E01 (overcurrent), E04 and E05 (low and high voltage), E07 (blocked rotor), E11 (dry-run protection) and E18 (temperature protection).
Key points
- Supply is 1×230 V 50/60 Hz; mains must stay within 230 V ±10%, otherwise E04 or E05 is raised.
- Fluid temperature is 0 to +110 °C and ambient 0 to +40 °C; at 40 °C ambient the permitted fluid range is 5 to 95 °C, at 25 °C ambient it is 5 to 110 °C.
- EEI ≤ 0.21, sound pressure level ≤ 55 dB(A), IP44, insulation class F, maximum operating pressure 10 bar.
- Minimum inlet pressure depends on fluid temperature: 0.05 bar (0.5 m) below 75 °C, 0.5 bar (5 m) at 75-90 °C, 1.08 bar (10.8 m) at 90-110 °C.
- Four control modes exist: constant speed, constant pressure (suited to underfloor heating), proportional pressure (suited to heating circulation) and AUTO SmartAdapt.
- For venting, the electronics are set to the highest constant-speed level and the pump runs at least 20 minutes; the automatic air-release programme lasts 5 minutes.
- After a power interruption wait at least 1 minute before restarting, otherwise the inrush current limiter does not engage.
- Supply cable cross-section must be at least 0.75 mm², and heat-resistant cable is needed in systems above 90 °C.
Using it in design
- When selecting the pump, check the fluid and ambient temperature pair against the permitted application range; for fluid above 95 °C the ambient is limited to 25 °C.
- Check suction-side pressure against the temperature class; above 90 °C the expansion vessel and static pressure must deliver at least 1.08 bar inlet pressure.
- Choose the control mode by load type: proportional pressure for radiator heating circuits, constant pressure for underfloor heating, AUTO SmartAdapt for dual-circuit systems with varying load.
- This series is meant for heating and low-viscosity fluids; confirm with the manufacturer before using it in data-centre chilled-water circuits or glycol mixes above 1:1.
- Add the 20-minute venting step, the 1-minute restart wait and the E-code fault table to the commissioning checklist.
Who should read it
Mechanical designers selecting circulation pumps for heating and auxiliary water circuits, and commissioning and maintenance teams.
Document contents
- Safety instructions
- Transport and storage
- Intended use
- Product data
- Pump description
- Pump settings
- Filling and venting the system
- Performance range
- Installation
- Electrical connection
- Maintenance and service
- Faults, causes and remedies
- Disposal
Publication details
- Authors
- Masdaf
- Publisher
- Masdaf
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public source opened on the access date. No open redistribution licence established; metadata and original short summaries only. No reliable publication year identified; upload timestamp is not used as publication year.
Citation
Masdaf OmniA 40 F / 50 F / 65 F: Kullanım Kılavuzu. Masdaf. https://cms.masdaf.com/Uploads/cd22e11e4e594b5f9eed5c002f2eee61.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.