Control-Aware Multi-Horizon PUE Forecasting for Coordinated Data Center Demand-Side Management and Microgrid Dispatch
Energies (MDPI AG) · Yingqi Liang, Junjie Peng et al.
A 2026 Energies paper links a Temporal Fusion Transformer that forecasts PUE from planned workload and cooling schedules to a model predictive controller, validated with an EnergyPlus simulation of a Shenzhen data centre.
On this page
Overview
The paper argues that a fixed PUE, or a forecast independent of planned controls, is inconsistent with demand-side management that coordinates workloads, cooling and on-site energy resources. The proposed control-aware framework forecasts PUE using planned workload and cooling schedules as inputs. A power-consistent Temporal Fusion Transformer (PC-TFT) predicts quantiles of non-IT overhead power and rack inlet temperature from telemetry, weather forecasts, admitted requests and candidate schedules.
Facility power and PUE are derived from an algebraic power balance, so PUE is never below 1. Conformal calibration quantifies uncertainty, and the forecasts feed a risk-informed model predictive controller that coordinates workloads, cooling, photovoltaic generation, battery storage and grid exchange. The framework is validated with EnergyPlus simulation of a Shenzhen data centre together with workload and microgrid simulations. The results report lower operating cost, lower peak grid demand, higher renewable utilisation and fewer service-quality violations than the baselines.
Key points
- PUE is forecast from planned workload and cooling schedules rather than a fixed value.
- The PC-TFT predicts quantiles of non-IT overhead power and rack inlet temperature.
- Facility power and PUE are derived from an algebraic power balance, keeping PUE at or above 1.
- Conformal calibration quantifies forecast uncertainty.
- Validation uses an EnergyPlus simulation of a Shenzhen data centre.
- Lower operating cost, lower peak grid demand and higher renewable utilisation are reported against baselines.
Using it in design
- For a facility planning demand-side management or microgrid dispatch, consider a PUE model tied to workload and cooling schedules instead of a fixed PUE.
- In BMS and DCIM design, plan for telemetry, weather forecast and schedule data to reach the forecasting and control layer.
- For sites with PV, battery and grid connection, include in concept design a control architecture that optimises cooling and workload schedules together with those sources.
- Results are simulation-based; validate against your own facility data in field use.
Who should read it
Engineers designing data-centre energy management, microgrids and control systems, and demand-side management researchers.
Related standards
- ISO/IEC 30134-2 (PUE)
Publication details
- Authors
- Yingqi Liang; Junjie Peng; Guanyu Fu; Dipti Srinivasan
- Publisher
- Energies (MDPI AG)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Yingqi Liang; Junjie Peng; Guanyu Fu; Dipti Srinivasan (2026). Control-Aware Multi-Horizon PUE Forecasting for Coordinated Data Center Demand-Side Management and Microgrid Dispatch. Energies (MDPI AG). https://doi.org/10.3390/en19163840
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.