TX2-FC-G04-Z: The free-cooling chiller dedicated to hyperscale and colocation data centers
Mitsubishi Electric Hydronics & IT Cooling Systems
Mitsubishi Electric Hydronics & IT Cooling Systems' TX2-FC-G04-Z is a free-cooling chiller range with magnetic-levitation oil-free centrifugal compressors on R1234ze, claiming 10-20% lower annual energy from its new control logic.
On this page
Overview
This brochure presents the Climaveneta TX2-FC-G04-Z range, designed for hyperscale and colocation data centres. It combines an oil-free magnetic-levitation centrifugal compressor, a flooded evaporator and free-cooling technology. Free-cooling and free-cooling no-glycol versions are offered. Sizes 1232, 1653 and 1803 are shown; the first two ship in a 40 ft HC container and all fit a standard truck.
Three elements drive the energy case. A low-lift pump lets the compressor run below the standard low-lift limit, widening its map at high leaving water temperatures. The new free-cooling logic claims 10-20% annual energy savings over traditional control; an example analysis for Frankfurt at 32/20 °C water shows about 18% lower annual consumption. W3000+ control manages compression ratio, speed, IGV position and bypass valve, keeping the compressor away from surge and current limits.
On design and environment: the range is developed for low-GWP R1234ze, with R513A also noted. Low absorbed power allows genset and power equipment to be downsized. Fast restart, ATS for transfer to a second supply, predictive maintenance through ClimaPRO+ and two-level alarm management support continuity; ClimaPRO+ handles redundancy management up to Tier IV.
References include Copenhagen (3,830 kW, 5 chillers), Oslo (5,550 kW, 8 chillers) and Munich (1,800 kW). Savings figures rest on manufacturer tests and depend on site climate and water temperature.
Key points
- Oil-free magnetic-levitation centrifugal compressor and flooded evaporator; free-cooling and no-glycol free-cooling versions.
- Three sizes: 1232, 1653 and 1803; the brochure capacity axis runs to 1,800 kW.
- Designed for R1234ze; R513A also offered.
- New free-cooling logic claims 10-20% annual energy savings, depending on water temperature and climate.
- Frankfurt, 32/20 °C water example: about 18% lower annual consumption than traditional logic.
- A low-lift pump widens the compressor map at high leaving water temperature.
- Ø910 mm EC fans; V-block structure; first two sizes ship in a 40 ft HC container.
- References: Copenhagen 3,830 kW (5 chillers), Oslo 5,550 kW (8 chillers), Munich 1,800 kW.
Using it in design
- Recompute the free-cooling saving claim (10-20%) with project climate and the water temperature pair; the Frankfurt 32/20 °C example is a single point.
- Evaluate in the power design whether the oil-free compressor's low starting current and absorbed power allow smaller genset and distribution.
- Confirm with the manufacturer how the low-lift pump affects the compressor map at high leaving water temperatures.
- On transport-limited sites, include 40 ft HC container and 13.6 m truck compatibility in the layout.
- Add ClimaPRO+ BMS integration to the specification for redundancy management and predictive maintenance.
Who should read it
Mechanical designers and owner representatives selecting free-cooling chillers for hyperscale and colocation data centres.
Document contents
- Optimised range
- Environmentally friendly R1234ze
- Minimum consumption, maximum efficiency
- Installation care and design for critical environments
- Technological choices
- New free-cooling management
- Energy analysis and ClimaPRO+
- W3000+ control logic
- References
Publication details
- Authors
- Mitsubishi Electric Hydronics & IT Cooling Systems
- Publisher
- Mitsubishi Electric Hydronics & IT Cooling Systems
- Year
- 2023
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Vendor brochure; no open licence stated
Citation
Mitsubishi Electric Hydronics & IT Cooling Systems (2023). TX2-FC-G04-Z: The free-cooling chiller dedicated to hyperscale and colocation data centers. Mitsubishi Electric Hydronics & IT Cooling Systems. https://www.mitsubishi-electric.co.nz/materials/PRODUCT/Chiller-Cooling/TX2-FC-G04-Z_1232-1803/00_Publications/02_Brochure/TX2-FC-G04-Z%201232%20-%201803%20Brochure.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.