Technical guideFree to read2022

SiC Semiconductors Increase UPS Reliability & Efficiency

Mitsubishi Electric Power Products, Inc. · National Sales Team, Critical Power Solutions Division, Mitsubishi Electric Power Products, Inc.

A 2022 Mitsubishi Electric Power Products white paper: a 500 kVA UPS with SiC MOSFETs cuts power losses by 70%, reaches 98.6% double-conversion efficiency and lowers heat loss by 39.4% at full load.

On this page

Overview

The paper traces the evolution of semiconductors in UPS power electronics. In the 1960s-80s, SCR-based UPS with square-wave output reached about 85% efficiency; IGBT in 1992 gave 94%; transformerless 3-level switching in 2008 gave up to 97%. In 2015 silicon carbide (SiC) MOSFETs replaced silicon IGBTs and efficiency rose to 98.6%. Much of the text is an introduction to semiconductor physics (bandgap, P-N junction).

Bandgap energies in its table are germanium 0.67 eV, silicon 1.11 eV, gallium arsenide 1.4 eV and silicon carbide 3.25 eV. Wide-bandgap (WBG) materials let devices run at higher voltage, frequency and temperature. According to the author, 100% SiC power-switching modules cut power losses by 70% and keep double conversion efficient even at low load, so ECO mode is no longer needed.

The numerical example is a 500 kVA SiC UPS: efficiency is 97.79% at 20% load, 98.66% at 50% and 98.20% at 100%. Heat rejection at 100% load is 69.2 kBTU/hr for a silicon UPS against 42.0 kBTU/hr for SiC (39.4% energy saving); the saving is 49.9% at 75% load and 46.9% at 50% load. Weight is 2770 lb against 3330 lb (17% less floor load) and floor area is 14 ft2 against 20 ft2 (30% less).

This is a manufacturer (Mitsubishi) article signed by the sales team, giving measurements for its own product; it is not an independent test report. It still serves as a reference for selection and cooling calculations because it shows the effect of SiC on UPS efficiency, heat and footprint numerically in one example.

Key points

  1. UPS efficiency history: SCR era about 85%, IGBT (1992) 94%, transformerless 3-level (2008) 97%, SiC MOSFET (2015) 98.6%.
  2. Bandgap: Ge 0.67 eV, Si 1.11 eV, GaAs 1.4 eV, SiC 3.25 eV; WBG is defined as at least about 2-3 eV.
  3. 100% SiC power-switching modules reduce semiconductor power losses by 70%.
  4. 500 kVA SiC UPS efficiency: 91.59% at 5% load, 95.09% at 10%, 97.79% at 20%, 98.66% at 50%, 98.56% at 75% and 98.20% at 100%.
  5. Heat rejection at 100% load is 42.0 kBTU/hr (SiC) instead of 69.2 kBTU/hr (Si); heat-loss energy savings are 39.4% at 100% load, 49.9% at 75% and 46.9% at 50%.
  6. Cooling accounts for about 35% of a data centre's electrical energy consumption.
  7. The 500 kVA SiC UPS weighs 2770 lb (conventional 3330 lb, 17% less floor load) and occupies 14 ft2 (conventional 20 ft2, 30% less).
  8. SiC's high efficiency at low load keeps double-conversion protection without resorting to ECO mode.

Using it in design

  • When comparing UPS, ask for the efficiency curve across 20-100% load instead of one peak value; for SiC units the curve stays high at low load.
  • Add UPS heat rejection (kW or kBTU/hr) to the cooling load; a SiC-based unit of the same rating shows markedly lower loss and heat rejection.
  • In rooms limited by floor loading or space, include the weight and footprint advantage of SiC units in the layout study.
  • Compare high-efficiency double conversion with ECO mode in total cost of ownership, and verify from product data whether similar savings are available without the protection loss of ECO mode.
  • Ask at bid stage for the measurement conditions of the supplier's data (load points, input and output power factor) and for an independent test certificate.

Who should read it

Design engineers selecting UPS and comparing efficiency, mechanical designers calculating cooling load, and facility owners.

Document contents

  1. Executive Summary
  2. UPS Mission
  3. UPS History
  4. UPS Basics: semiconductor, current flow, analysis of materials
  5. Wide Bandgap Materials
  6. Introducing the Game Changer: SiC
  7. Size and Weight
  8. Summary

Related standards

  • IEC 62040-3

Publication details

Authors
National Sales Team, Critical Power Solutions Division, Mitsubishi Electric Power Products, Inc.
Publisher
Mitsubishi Electric Power Products, Inc.
Year
2022
Document number
SA-ENL0025R2
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Vendor white paper, free PDF; no open licence stated.

Citation

National Sales Team, Critical Power Solutions Division, Mitsubishi Electric Power Products, Inc. (2022). SiC Semiconductors Increase UPS Reliability & Efficiency. Mitsubishi Electric Power Products, Inc.. SA-ENL0025R2. https://mitsubishicritical.com/wp-content/uploads/2025/02/sa-enl0025-sic-semiconductors-increase-ups-reliability-efficiency.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.